146
Photo 4
Photo 3
Photo 2
Continued to the next page.
Electrical
parts box
Noise filter circuit
board (N.F.)
Terminal cover
Compressor
(MC)
Valve bed
Terminal
block (TB2)
Controller
circuit
board (C.B.)
Terminal
block (TB1)
PUHZ-RP100YKA PUHZ-RP125YKA
PUHZ-RP140YKA
Fan motor
fixing screws
Fan motor
Fan motor
fixing screws
Front panel
Propeller
Nut
Photo 1
Top panel fixing screws
Top panel
Service panel
fixing screws
Service panel
Grille
fixing
screws
Grille
fixing
screws
Slide
Cover panel
fixing screws
Reactors
1. Removing the service panel and top panel
(1)
Remove the service panel fixing screws (3 for front, 5 × 12)
and slide the hook on the right downward to remove the
service panel.
(2)
Remove the top panel fixing screws (3 for front, 3 for rear,
5 × 12) to detach the top panel.
Side panel (R)
2. Removing the fan motor (MF1, MF2)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3)
Remove the fan grille fixing screws (4 for front, 5 × 12) to
detach the fan grille. (Top and bottom) (See Photo 1)
(4)
Remove a nut (for right handed screw of M6) to detach the
propeller. (Top and bottom) (See Photo 2)
(5)
Disconnect the connectors, CNF1, CNF2 on controller
circuit board in electrical parts box.
(6)
Remove the fan motor fixing screws (4 for front, 5 × 20) to
detach the fan motor. (See Photo 3)
3. Removing the electrical parts box
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3)
Disconnect the indoor/outdoor connecting wire from
terminal block.
(4)
Disconnect the connector CNF1, CNF2, LEV-A and LEV-B,
LEV-C (RP140) on the controller circuit board.
<Symbols on the board>
• CNF1, CNF2 : Fan motor
• LEV-A, LEV-B, LEV-C : LEV
(5)
Disconnect the pipe-side connections of the following parts.
•
Thermistor
<Liquid>(TH3)
•
Thermistor
<Discharge>(TH4)
• Thermistor <Outdoor 2-phase pipe>(TH6)
•
Thermistor
<Ambient>(TH7)
• Thermistor <Comp. surface> (TH32)
• Thermistor <Ref. check> (TH33)
• High pressure switch (63H)
• 4-way valve coil (21S4)
(6) Disconnect the lead wires from the reactors.
(7)
Disconnect the lead wires from 3 clamps on the separator.
OPERATING PROCEDURE
PHOTOS & ILLUSTRATION
OCH451D