114
OPERATING PROCEDURE
PHOTOS
Photo 9
5. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
and thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Disconnect the connectors, TH7/6 (red) on the controller
circuit board in the electrical parts box.
(4) Loosen the 2 wire clamps on top of the electrical parts box.
(5) Pull out the thermistor <Outdoor 2-phase pipe> (TH6) and
thermistor <Outdoor> (TH7) from the sensor holder.
Note: In case of replacing thermistor <Outdoor 2-phase
pipe> (TH6) or thermistor <Outdoor> (TH7), replace
it together.
6. Removing the thermistor <Discharge> (TH4)
(1) Remove the service panel. (See Figure 1)
(2) Disconnect the connector TH4 (white) on the controller
circuit board in the electrical parts box.
(4) Loosen the wire clamps bottom of the electrical parts box
and separator.
(5) Pull out the thermistor <Discharge> (TH4) from the sensor
holder.
Photo 12
7. Removing the thermistor <Outdoor pipe> (TH3) (TH32) (TH33)
(1) Remove the service panel. (See Figure 1)
(2) Disconnect the connectors, TH3 (white) and TH32 (black),
TH33 (yellow) on the controller circuit board in the
electrical parts box.
(3) Loosen the wire clamps bottom of the electrical parts box
and separator.
(4) Pull out the thermistor <Outdoor pipe> (TH3), (TH32),
(TH33) from the sensor holder.
(TH33 : See Photo 15)
Photo 11
Photo 10
Lead wire of
thermistor
<Outdoor>
(TH7)
Sensor holder
Clamp
Muffler
Separator
Compressor
(MC)
Thermistor
<Discharge>
Clamp
(for TH3)
Thermistor <Outdoor pipe> (TH3)
Power
receiver
Thermistor
<Outdoor pipe>
(TH32)
Low pressure
switch(63L)
Photo 13
Clamp
Thermistor
<Outdoor 2-phase pipe>(TH6)
Electrical parts box
OCH425D