11
6-4. STANDARD OPERATION DATA
To
ta
l
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Representative matching
SHF
BF
W
kW
Mode
Capacity
Input
PEAD-RP71JA
PEAD-RP71JA
Cooling
7,100
2.15
Heating
8,000
2.34
8.09
2.46
0.92
68
42
14
7.5
27
19
15
35
24
0.85
0.13
8.94
2.71
0.76
74
43
5
7.5
20
15
38
7
6
—
—
1 , 50
230
1 , 50
230
Phase , Hz
Voltage
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
A
V
A
MPa
MPa
m
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
PEAD-RP100JA
PEAD-RP125JA
PEAD-RP100JA
PEAD-RP125JA
Cooling
10,000
3.06
Heating
11,200
3.10
Cooling
12,500
3.89
Heating
14,000
3.88
11.10/3.69
2.61
0.97
68
44
13
7.5
27
19
16
35
24
0.89
0.18
11.28/3.74
2.22
0.72
65
37
4
7.5
20
15
35
7
6
—
—
4.92
2.79
0.89
72
47
8
7.5
27
19
15
35
24
0.85
0.09
4.91
2.70
0.70
76
44
1
7.5
20
15
39
7
6
—
—
1 , 50
230
1/3 , 50
230/400
1 , 50
230
3 , 50
400
PUHZ-HRP100VHA(2)
PUHZ-HRP100YHA(2)
PUHZ-HRP125YHA(2)
PUHZ-HRP71VHA(2)
1.28
1.17
1.68
1.57
2.40
2.29
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/cm
2
)