19
19
CN51
Multiple remote
controller adapter
PAC-SA88HA-E
Indoor controller board
Distance between indoor
controller board and relay
must be within 10m.
Be sure to secure insulation
material by tape, etc
5
Green
Yellow
Orange
Connector (5P)
Indoor unit side
Multiple remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape, etc
Installation at site
CN51
on
indoor
controller
board
Red
Brown
1
~
CN51
MB
5-3. OPERATION IN CONJUNCTION WITH
DUCT FAN (Booster fan)
• Whenever the indoor unit is operating, the duct fun also
operates.
(1) Connect the optional multiple remote controller adapter
(PAC-SA88HA-E) to the connector CN51 on the indoor
controller board.
(2) Drive the relay after connecting the 12V DC relay
between the Yellow and Orange connector wires.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (For DC 12V, coil rating : 1.0W or below)
Branch duct hole
14-
:
2.8 burring hole
Indoor unit
:
150 cut out hole
Fresh air intake hole
:
175 burring hole pitch
Drain pipe
Fresh air intake hole diagram
Refrigerant pipe
3-
:
2.8 burring hole
Branch duct hole diagram
(view from either side)
:
125 burring
hole pitch
:
100 cut
out hole
Ceiling
*158
120
120
350
90
70°
100
100
90
100
130
*155
*167
5-2. BRANCH DUCT HOLE AND FRESH AIR INTAKE HOLE
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when
required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figures marked with * in the drawing below represent the dimensions of the main unit excluding those of the optional multi
function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise, condensation and dripping may occur.
OCH413D