32
9-3. TEST POINT DIAGRAM
9-3-1. Indoor controller board
PLFY-P32/40/50/63/80/100/125VBM-E.UK PLFY-P32/40/50/63/80VBM-E
1
.UK
PLFY-P32/40/50/63/80/100/125VBM-ER2.UK PLFY-P32/40/50/63/80/100/125VBM-ER3.UK
The voltage range of DC12V in this page
is between DC11.5 V to DC 13.7 V.
CN2M
Connect to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30VDC (non-polar)
CN3A
Connect to the terminal block (TB15)
(MA-Remote controller connecting wire)
1
-
3
: 8.7-13V DC (Pin
1
(+))
LED2
Power supply for
MA-Remote controller
CN32
Remote switch
SW4
Model selection
SW3
Function setting
SW2
Capacity setting
CN6Y
i-See sensor motor output
12VDC pulse output
FUSE
6.3A 250V
SWE
Test run(Drain pump)
Jumper wire J41, J42
Pair No.setting for wireless
remote controller
CND
Power supply for indoor
controller board
3
-
5
: 220-240VAC
CNV
vane motor output
12VDC pulse
CN4Y
i-See sensor
CN60
Linear expansion valve (LEV)
output
12VDC pulse output
CN44
Pipe temperature thermistor
1
-
2
: Liquid (TH22)
3
-
4
: Gas (TH23)
CN4F
Drain float switch (FS)
CN20
Room temperature
thermistor (TH21)
CN27
Damper signal output
12VDC(
1
: +)
CN3G
Auto grille signal output
CN90
Connect to the wireless
remote controller board
(W.B)
LED1
Main power supply
(Indoor unit : 220-240V)
CNMF
Connect to the
fan motor (MF)
1
-
4
: DC310~340V
5
-
4
: DC15V
CNP
Drain pump output (DP)
1
-
3
: 220-240VAC
CNAC
Auto grille power
(220-240VAC)
CN51
Centrally control
1
-
2
:
Control signal
12VDC pulse input (
1
:
+)
3
-
4
:
Operation indicator
12VDC (
3
:
+)
3
-
5
:
Malfunction indicator
12VDC (
3
:
+)
CN52
Remote indicator
1
-
2
: Status lamp 12VDC (
1
: +)
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
1
-
3
: Cooling/Dry status lamp
12VDC (
1
: +)
1
-
4
: Heating status lamp
12VDC (
1
: +)
OCH413D