32
4. STANDARD OPERATION DATA
Total
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Service Ref.
SHF
BF
V
A
V
A
MPa
MPa
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
Mode
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
1 , 50
240
PUH-P1.6VGA/YGA
1/3 , 50
240/415
1 , 50
240
PUH-P2VGA/YGA
1/3 , 50
240/415
1 , 50
240
PUH-P2.5VGA
1
/YGA
1
1/3 , 50
240/415
0.55
7.43/2.67
2.02
0.50
78.5
52.4
8.1
5
27
19
14.0
35
24
0.72
0.21
0.55
7.43/2.86
2.02
0.43
76.9
—
-0.3
5
20
15
38.1
7
6
—
—
0.63
10.39/3.88
2.35
0.51
85.3
55.2
7.0
5
27
19
13.6
35
24
0.74
0.19
0.63
9.36/4.02
2.37
0.41
83.2
—
-1.2
5
20
15
39.6
7
6
—
—
0.72
11.27/4.11
2.16
0.52
78.5
49.6
8.3
5
27
19
13.8
35
24
0.71
0.19
(22.0)
(5.3)
(21.8)
(4.1)
(24.0)
(5.2)
(24.2)
(4.2)
(20.6)
(5.1)
(kgf/
F
)
(kgf/
F
)
(20.6)
(4.4)
0.72
10.32/4.03
2.14
0.40
76.1
—
-1.3
5
20
15
39.1
7
6
—
—
Indoor unit
Service Ref.
PEHD-P1.6EAH
PEHD-P2EAH
PEHD-P2.5EAH
PEAD-P1.6EA
PEAD-P2EA
PEAD-P2EA
PEHD-P1.6EAH
PEHD-P2EAH
PEHD-P2.5EAH
PEAD-P1.6EA
PEAD-P2EA
PEAD-P2EA
Capacity
Input
With Electric heater
Without Electric heater
With Electric heater
Without Electric heater
W
kW
Cooling
4,500
1.75
Heating
4,900
1.80
Cooling
5,550
2.44
Heating
6,150
2.22
Cooling
6,700
2.68
Heating
7,200
2.45
D.B.
W.B.
D.B.
D.B.
W.B.
Heat pump type Rating Conditions (ISO T1)
The unit of pressure has been changed to Mpa based on international SI system.
The conversion factor is : 1 (Mpa) = 10.2 (kgf/cm
2
)