The wiring is different when the remote controller is connected to a CITY MULTI control system (“-A”
type and later) and when it is connected to a Mr. SLIM air conditioner (A control type). The wiring also
differs with the system configuration. Check the system used.
1. Connecting to CITY MULTI control system
The numbers (1) to (4) in the figure correspond to items (1) to (4) in the following description.
(1) Wiring from the remote controller
• Connect to the MA remote controller terminal block (TB15) on the indoor unit.
• The terminal block has no polarity. Connect to the terminal block at the bottom of the remote
controller case.
(2) Operating in a group (Groups 03, and 04 above)
• Interconnect the MA remote controller terminal block (TB15) of the indoor units you want to
operate as a group, and connect the MA remote controller to that point.
• When the remote controller is used in combination with the system controller as shown in the
figure above, group setting at the system controller (central controller in the figure above) is
necessary.
(3) Number of connectable remote controllers
• Only one remote controller can be connected to a group made up of indoor units.
• The MA Touch Remote Controller cannot be used in combination with other MA remote
controllers.
(4) To interlock to a LOSSNAY or OA processing unit, make the following settings using the remote
controller. (For a description of how to set an interlock, see section 11 “Service menu” (5)
“LOSSNAY setting”.)
Set the LOSSNAY or OA processing unit address and the address of all the indoor units you want
to interlock.
(5) Total length of remote controller wiring
• The MA Touch Remote Controller can be wired up to 70 m (229 ft).
5
How To Wire Transmission Line
Connect to TB15
on the indoor unit.
a
Outdoor unit
b
Indoor unit
c
LOSSNAY or
OA processing unit
d
Touch Remote Controller
e
Central controller
f
Power supply unit for
transmission line
TB5 TB15
TB5 TB15
b
b
TB5 TB15
c
TB5 TB15
b
TB5 TB15
b
TB5 TB15
b
TB5 TB15
b
TB7 TB3
TB5 TB15
TB5 TB15
TB7 TB3
(1)
(1)
(3)
(3)
(3)
(3)
(2)
(2)
(2)
(4)
(1)
(1)
a
a
d
d
d
d
b
b
e
f
Address = 51
Address = 01
Address = 02
Address = 55
Address = 08
Address = 07
Address = 03 Address = 04
Address = 09
Address = 06
Address = 05
Group 01
Group 02
Group 03
Group 04
NOTE: When interlocking the MA remote controller with a LOSSNAY or OA processing unit,
always set the address of all the indoor units in the group and the address of the
LOSSNAY or OA processing unit.
WT08580X01.book 7 ページ 2017年6月19日 月曜日 午後2時1分
Summary of Contents for PAR-CT01MAA-PB
Page 30: ... 30 GB ...
Page 60: ... 30 F ...
Page 90: ... 30 ES ...
Page 120: ... 30 I ...
Page 150: ... 30 PR ...
Page 180: ... 30 GR ...
Page 210: ... 30 TR ...
Page 240: ... 30 SW ...
Page 270: ... 30 D ...
Page 300: ... 30 NL ...
Page 330: ... 30 RU ...
Page 360: ... 30 CZ ...
Page 390: ... 30 HG ...
Page 420: ... 30 PO ...
Page 450: ... 30 DK ...
Page 451: ......