2. Connecting to Mr. SLIM air conditioner
The remote controller wiring depends on the system configuration. Check the system configuration.
Wire the remote controller as shown in the example below.
The numbers (1) to (3) in the figure correspond to items (1) to (3) in the following description.
[1] Connecting the remote controller for each refrigerant system (Standard 1:1, simultaneous twin,
simultaneous triple, simultaneous four)
[2] When grouping by different refrigerant systems
* Set the refrigerant address using the outdoor unit dip switches. (For more information, refer to the
outdoor unit installation manual.)
* All the indoor units enclosed in
are controlled as one group.
(1) Wiring from remote controller
• Connect to indoor unit TB5 (remote controller terminal block). (The terminal block has no polarity.)
• For simultaneous multi type, when mixing various types of indoor units, always connect the
remote controller to the indoor unit with the most functions (wind velocity, vane, louver, etc.).
(2) When grouping with difference refrigerant systems
• Group using the remote controller wiring. Connect the remote controller to an arbitrary indoor unit
of each refrigerant system you want to group.
• When mixing different types of indoor units in the same group, always make the outdoor unit
connecting the indoor unit with the most functions (wind velocity, vane, louver, etc.) the Main unit
(refrigerant address = 00). Also, when the Main unit is the simultaneous multi type, always satisfy
the conditions of (1) above.
• The MA Touch Remote Controller can control up to 16 refrigerant systems as one group.
(3) Only one remote controller can be connected to each group. The remote controller cannot be
used in combination with other MA remote controllers.
Connect to TB5
on the indoor unit.
a
Outdoor unit
b
Indoor unit
d
Touch Remote Controller
(1)
TB5
TB4
TB1
TB4
(3)
a
b
b
d
Refrigerant
address = 00
Simultaneous twin
TB4
TB4
TB4
TB4
TB4
TB4
TB1
TB1
TB1
TB5
TB5
TB5
(2)
(1)
(3)
(2)
a
a
a
b
b
b
b
b
b
d
Standard 1:1 Simultaneous twin
Simultaneous triple
Refrigerant
address = 01
(Sub)
Refrigerant
address = 00
(Main)
Refrigerant
address = 02
(Sub)
WT08580X01.book 8 ページ 2017年6月19日 月曜日 午後2時1分
Summary of Contents for PAR-CT01MAA-PB
Page 30: ... 30 GB ...
Page 60: ... 30 F ...
Page 90: ... 30 ES ...
Page 120: ... 30 I ...
Page 150: ... 30 PR ...
Page 180: ... 30 GR ...
Page 210: ... 30 TR ...
Page 240: ... 30 SW ...
Page 270: ... 30 D ...
Page 300: ... 30 NL ...
Page 330: ... 30 RU ...
Page 360: ... 30 CZ ...
Page 390: ... 30 HG ...
Page 420: ... 30 PO ...
Page 450: ... 30 DK ...
Page 451: ......