17
5. Zone Remote Controller
6
Connect the remote controller cable to the terminal block on the top case.
Connect the remote controller cable to the terminal block.
Take the following procedure only when performing direct wall installation and
drilling a hole in the wall.
• Seal the hole through which the cable is threaded with putty.
<Fig. 5.1.10>
<Fig. 5.1.11>
To reduce the risk of electric shock, shorting, or malfunctions, keep wire piec-
es and sheath shavings out of the terminal block.
Do not use solderless terminals to
connect cables to the terminal block.
Solderless terminals may come in
contact with the circuit board and
cause malfunctions or damage the
controller cover.
Hold the cables in place with clamps
to prevent undue force from being
applied to the terminal block and
causing cable breakage.
Important
7
Set the M-NET addresses.
To set the address, turn the rotary switch with a precision slotted screwdriver
[(-), 2.0mm (1/16 in) (W)] to a torque of less than 19.6 N to avoid the damage
to the rotary switches.
Important
Address range
Address setting method
Main remote controller
101
Not necessary since it is set to 101 as
initial setting.
Note:
M-NET address can be changed with or without the power being applied to
the controller.
The screen will jump to the [Start-up] screen.
Zone settings will be deleted, but the rest of the information will be retained.
<Fig. 5.1.12>
Rotary switches
(Ex: Address 101)
012
3
45
67
8
9
012
3
45
67
8
9
10s digit
(tens digit)
(Above)
1s digit
(ones digit)
(Below)
Connect the cable
to the terminal
block, and insert
the cable into the
groove.
Remote
controller cable
Seal the gap with putty.