57
MXZ-6C
Upper or
left lamp of
OPERATION
INDICATOR
lamp (Indoor
unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition
Remedy
Indoor/
outdoor
unit failure
mode
recall
function
LED 1
LED 2
OFF
None (Normal)
Lighting
Lighting
2-time fl ash
Outdoor power system
Lighting
Lighting
Overcurrent protection cut-out operates
3 consecutive times, bus-bar voltage
protection cut-out operates 3 consecu-
tive times, or primary current protection
cut-out operates 3 consecutive times
within 1minute after the compressor
gets started.
• Check the connection of
the compressor connecting
wire.
• Refer to 11-6. How to
check inverter/compressor.
• Check the stop valve.
○
3-time fl ash
Discharge temperature thermis-
tor
Lighting
Once
Thermistor shorts or opens during
compressor running.
• Refer to 11-6. "Check of
outdoor thermistors".
○
Defrost thermistor
Lighting
Once
Ambient temperature thermistor
Lighting
Twice
Fin temperature thermistor
Lighting
3 times
• Replace the power board.
P.C. board temperature thermis-
tor
Lighting
4 times
• Replace the power board.
Outdoor heat exchanger tem-
perature thermistor
Lighting
9 times
• Refer to 11-6. "Check of
outdoor thermistors".
4-time fl ash
Overcurrent
Once
Goes out 49 A current fl ows into intelligent power
module.
• Reconnect compressor con-
nector.
• Refer to 11-6. "How to
check inverter/compressor".
• Check the stop valve.
—
Out-of-step protection
9 times
Goes out Waveform of compressor current is dis-
torted.
• Refer to 11-6. " How to
check inverter/compressor.
5-time fl ash
Discharge temperature
Lighting
Lighting
Discharge temperature exceeds 114 °C
during operation.
Compressor can restart if discharge
temperature thermistor reads 100 °C or
less 3 minutes later.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6. "Check of
LEV".
—
6-time fl ash
High pressure
Lighting
Lighting
High-pressure is detected with the
high-pressure switch (HPS) during op-
eration.
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
—
The outdoor heat exchanger tempera-
ture exceeds 70 °C during cooling or
the indoor gas pipe temperature ex-
ceeds 70°C during heating.
7-time fl ash
Fin temperature
3 times
Goes out The fin temperature exceeds 110 °C
during operation.
• Check around outdoor unit.
• Check outdoor unit air pas-
sage.
• Refer to 11-6. "Check of
outdoor fan motor".
—
P.C. board temperature
4 times
Goes out The P.C. board temperature exceeds
95 °C during operation.
8-time fl ash
Outdoor fan motor
Lighting
Lighting
Failure occurs 3 consecutive times
within 30 seconds after the fan gets
started.
• Refer to 11-6. "Check of
outdoor fan motor".
—
9-time fl ash
Nonvolatile memory data
Lighting
5 times
Nonvolatile memory data cannot be
read properly.
• Replace the outdoor control
P.C. board.
• Replace the power board.
○
10-time fl ash
Discharge temperature
Lighting
Lighting
The frequency of the compressor is
kept 80Hz or more and the discharge
temperature is kept under 50 °C (cool-
ing)/40 °C (heating) for more than 40
minutes.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6. "Check of
LEV".
—