5
COOLING INDOOR
Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C
OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°C
HEATING INDOOR
Dry-bulb temperature 20.0°C
OUTDOOR Dry-bulb temperature 7.0°C
Wet-bulb temperature 6.0°C
1 Measured under rated operating frequency.
2 Electrical data is for only outdoor unit.
NOTE: Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
Outdoor model
Indoor units number
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity [Rated (Min.-Max.) Hz]
Dehumidification
Outdoor air flow
Breaker capacity
Running current
Power input
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance (at 20 °C)
Model
Winding
resistance (at 20°C)
Dimensions W x H x D
Weight
Sound level
Fan speed
Refrigerant filling
capacity (R410A)
Refrigeration oil (Model)
m
m
m
m
kW
/h
m
3
/h
A
A
W
%
A
A
A
W
Ω
Ω
mm
kg
dB
rpm
kg
L
Compressor
2 Electrical
data
Fan
motor
Special
remarks
Capacity
System
Coefficient of performance(C.O.P)
MXZ-3C68VA
Single phase
230 V, 50 Hz
1 to 3
Max. 60
Max. 25
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
25
99
9.00
0.2
SNB172FEGH1T
1,800
U-V 0.72
V-W 0.72 W-U 0.72
RC0J60-CB
BLK-WHT 15.2
WHT-RED 15.2 RED-BLK 15.2
840 x 710 x 330
57
2.7
0.7 (NEO22)
Cooling
6.8 (2.9-8.4)
—
2,526
7.80
1,775
7.60
3.83
48
650
Heating
8.6 (2.6-10.6)
—
2,580
9.00
2,050
8.80
4.20
52
660
Outdoor unit power supply