background image

En-5

4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

•  Description of the function:

  With this function, once the operation mode is locked to either COOL/DRY mode 

or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “1” of SW1 on the outdoor display board to ON to enable this function.

3) To lock the operation mode in COOL/DRY mode, set the “2” of SW1 on the 

outdoor display board to OFF. To lock the operation in HEAT mode, set the 

same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:

  With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 

However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Lower the operating noise

[How to lower the operating noise]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “3” of SW1 on the outdoor display board to ON to enable this function.

3) Turn on the main power for the air conditioner.

4-5. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Turn off the breaker.

2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

3) Fully close the stop valve on the liquid pipe side of the outdoor unit.

4) Turn on the breaker.

5) Start the emergency COOL operation on all the indoor units.

6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

), fully close the stop valve on the gas pipe side of the outdoor unit and 

stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)

  *  If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.05 MPa [Gauge] (approx. 0.5 kgf/cm

2

), or the protec

-

tion function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect 

all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been 

relocated.

7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.

The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

 WARNING

4-6. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

COOL/DRY

HEAT

5.  PUMPING DOWN

BH79A129H01_en.indd   5

10/31/2014   9:57:28 AM

Summary of Contents for MXZ-2HJ40VA

Page 1: ...s the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Kurulum Kılavuzu TESİSATÇI İÇİN Bu kılavuzda yalnızca dış ünitenin kurulumu açıklanmaktadır İç ünite kurulum işlemini yaparken iç ünite kurulum kılavuzuna bakın English is original Orijinalin çevirisi ...

Page 2: ... leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could cause the pipes to burs...

Page 3: ... inner diameter or hard PVC pipe VP16 for drain socket 1 1 Note 1 Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit Units should be installed by licensed contractor according to local code requirements More than 100 mm More than 100 mm More than 200 mm if ther...

Page 4: ...r unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Indoor outdoor unit connecting wire OUTDOOR UNIT 35 mm 15 mm Lead wire Terminal block UNIT U...

Page 5: ... cap of service port to obtain the initial status 10 Leak test WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely Stop valve for GAS Stop valve cap Torque 19 6 to 29 4 N m 200 to 300 kgf cm Gauge manifold valve for R410A Compound pressure gauge for R41...

Page 6: ...he test run one by one Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner When relocating or disposing of the air conditioner pump down the system following the procedure below so...

Page 7: ...tuutettu EU edustaja joka on valtuutettu laatimaan teknisen eritelmän on mainittu alla Наш упълномощен представител в ЕС който е упълномощен да състави техническото досие е както следва MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K Yoji SAITO Product Marketing Director Issued 9 October 2014 Tomoyuki MIWA THAILAND Manager Quality Assurance Department MIT...

Reviews: