background image

En-2

*2

*2

*2

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

Port size of outdoor unit

Optional different-diameter joints (port size of outdoor unit → diameter of connection pipe)

MXZ-2HJ40VA

Liquid / Gas

6,35 (1/4) → 9,52 (3/8) : PAC-493PI

9,52 (3/8) → 12,7 (1/2) : MAC-A454JP

9,52 (3/8) → 15,88 (5/8) : PAC-SG76RJ

12,7 (1/2) → 9,52 (3/8) : MAC-A455JP

12,7 (1/2) → 15,88 (5/8) : MAC-A456JP

Refer to the installation manual of indoor unit for the diameter of connection pipe of indoor unit.

A , B UNIT

6,35 (1/4) / 9,52 (3/8)

1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunshine can be avoided as much as possible.

•  Where neighbours are not annoyed by operation sound or hot air.

•  Where rigid wall or support is available to prevent the increase of opera

-

tion sound or vibration.

•  Where there is no risk of combustible gas leakage.

•  When installing the unit, be sure to secure the unit legs.

•  Where it is at least 3 m away from the antenna of TV set or radio. Opera

-

tion of the air conditioner may interfere with radio or TV reception in areas 

where reception is weak. An amplifier may be required for the affected 

device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or blowing snow. In 

areas with heavy snow, please install a canopy, a pedestal and/or some 

baffle boards.

Note:

It is advisable to make a piping loop near outdoor unit so as to reduce 

vibration transmitted from there.

(Unit: mm (inch))

1-5. INSTALLATION DIAGRAM

ACCESSORIES

Check the following parts before installation.

(1) Drain socket

1

PARTS TO BE PROVIDED AT YOUR SITE

(A) Power supply cord*1

1

(B) Indoor/outdoor unit connecting wire*1

1

(C) Extension pipe

1

(D) Wall hole cover

1

(E)

Piping tape

1

(F)

Extension drain hose 

(or soft PVC hose, 15 mm inner 

diameter or hard PVC pipe VP16)

1

(G) Refrigeration oil

Little 

amount

(H) Putty

1

(I) Pipe fixing band

2 to 7

(J) Fixing screw for (I)

2 to 7

(K) Wall hole sleeve

1

(L)

Soft PVC hose, 15 mm inner 

diameter or hard PVC pipe VP16 

for drain socket (1)

1

Note:

*1 Place indoor/outdoor unit connecting wire (B) and 

power supply cord (A) at least 1 m away from the 

TV antenna wire.

The “Q’ty” for (B) to (K) in the above table is quan

-

tity to be used per indoor unit.

Units should be installed by licensed contractor according to local code requirements.

More than 

100 mm

More than 100 mm 

More than 200 mm if there are 

obstacles to both sides

Open as a rule

More than 500 mm if the back, 

both sides and top are open

More than 350 mm

Outdoor unit installation

(Unit: mm)

285

Air inlet

150

500

Air inlet

4-10 × 21 Oval holes

304~325

344.5

Air outlet

800

Open as a rule

More than 500 mm if the front 

and both sides are open

Note: 

When operating the air conditioner in low outside temperature, be sure 

to follow the instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side 

may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet 

side facing the wall.

•  To prevent exposure to wind, it is recommended to install a baffle board 

on the air outlet side of the outdoor unit.

Avoid the following places for installation where air conditioner trouble 

is liable to occur.

•  Where flammable gas could leak.

•  Where there is much machine oil.

•  Where oil is splashed or where the area is filled with oily smoke (such 

as cooking areas and factories, in which the properties of plastic could 

be changed and damaged).

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.

•   Where there is emission of high levels of VOCs, including phthalate 

compounds, formaldehyde, etc., which may cause chemical cracking.

*2 The manufacturing year and month is indicated on the spec 

name plate.

When the piping is to be attached 

to a wall containing metals (tin 

plated) or metal netting, use a 

chemically treated wooden piece 

20 mm or thicker between the wall 

and the piping or wrap 7 to 8 turns 

of insulation vinyl tape around 

the piping.

To use existing piping, perform 

COOL operation for 30 minutes 

and pump down before removing 

the old air conditioner. Remake 

flare according to the dimension 

for new refrigerant.

After the leak test, apply insulat

-

ing material tightly so that there 

is no gap.

BH79A129H01_en.indd   2

10/31/2014   11:29:48 AM

Summary of Contents for MXZ-2HJ40VA

Page 1: ...s the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Kurulum Kılavuzu TESİSATÇI İÇİN Bu kılavuzda yalnızca dış ünitenin kurulumu açıklanmaktadır İç ünite kurulum işlemini yaparken iç ünite kurulum kılavuzuna bakın English is original Orijinalin çevirisi ...

Page 2: ... leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could cause the pipes to burs...

Page 3: ... inner diameter or hard PVC pipe VP16 for drain socket 1 1 Note 1 Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit Units should be installed by licensed contractor according to local code requirements More than 100 mm More than 100 mm More than 200 mm if ther...

Page 4: ...r unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Indoor outdoor unit connecting wire OUTDOOR UNIT 35 mm 15 mm Lead wire Terminal block UNIT U...

Page 5: ... cap of service port to obtain the initial status 10 Leak test WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely Stop valve for GAS Stop valve cap Torque 19 6 to 29 4 N m 200 to 300 kgf cm Gauge manifold valve for R410A Compound pressure gauge for R41...

Page 6: ...he test run one by one Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner When relocating or disposing of the air conditioner pump down the system following the procedure below so...

Page 7: ...tuutettu EU edustaja joka on valtuutettu laatimaan teknisen eritelmän on mainittu alla Наш упълномощен представител в ЕС който е упълномощен да състави техническото досие е както следва MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K Yoji SAITO Product Marketing Director Issued 9 October 2014 Tomoyuki MIWA THAILAND Manager Quality Assurance Department MIT...

Reviews: