background image

10

4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

•  Description of the function:
 

With this function, once the operation mode is locked to either COOL/DRY mode 
or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “1” of SW1 on the outdoor display board to ON to enable this function.
3) To lock the operation mode in COOL/DRY mode, set the “2” of SW1 on the 

outdoor display board to OFF. To lock the operation in HEAT mode, set the 
same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:
  With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 

However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Lower the operating noise

[How to lower the operating noise]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “3” of SW1 on the outdoor display board to ON to enable this function.
3) Turn on the main power for the air conditioner.

4-5. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

Make sure that the following is done.
•  Power is supplied to the unit.
•  Stop valves are open.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Turn off the breaker.

2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3) Fully close the stop valve on the liquid pipe side of the outdoor unit.
4) Turn on the breaker.
5) Start the emergency COOL operation on all the indoor units.
6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

), fully close the stop valve on the gas pipe side of the outdoor unit and 

stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)

  *  If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.05 MPa [Gauge] (approx. 0.5 kgf/cm

2

), or the protec-

tion function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect 
all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been 
relocated.

7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.

The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

 

WARNING

4-6. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

COOL/DRY

HEAT

5.  PUMPING DOWN

VG79Y196H02.indd   10

2020/05/27   11:45:09

Summary of Contents for MXZ-2F52VF

Page 1: ...XZ 2F52VF English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit VG79Y196H02 indd 1 2020 05 27 11 45 06 ...

Page 2: ...l cover of the indoor unit and or the service panel of the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc n When installing relocating or servicing the unit make sure that no substance other than the specified refrigerant R32 enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pres sure rise an...

Page 3: ...alloy seamless pipe 5 Be careful not to crush or bend the pipe during pipe bending 6 Refrigerant pipe bending radius must be 100 mm or more 7 Insulation material Heat resisting foam plastic 0 045 specific gravity 8 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage 9 If the o...

Page 4: ... in a sufficiently large space without depressions 1 4 1 Minimum installation area for Outdoor units If you unavoidably install a unit in a space where all four sides are blocked or there are depressions confirm that one of these situations A B or C is satisfied Note These countermeasures are for keeping safety not for specification guarantee A Secure sufficient installation space minimum installa...

Page 5: ... the height from the floor to the bottom of the indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more for floor standing refer to indoor unit Installation manual There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15...

Page 6: ... M kg Amin m 1 00 No requirements 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 84 3 63 1 90 3 75 2 00 3 95 2 10 4 15 2 20 4 34 2 30 4 54 2 40 4 74 h0 Refer to indoor unit installation manual Floor standing VG79Y196H02 indd 5 2020 05 27 11 45 07 ...

Page 7: ...When the piping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for ...

Page 8: ...SE R32 REFRIGERANT Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contaminants...

Page 9: ... Use a joint pipe if the connection of the indoor unit differs Use tightening torque table above as a guideline for indoor unit side union joint section and tighten using two wrenches Excessive tightening dam ages the flare section 1 Apply a thin coat of refrigeration oil G to the flared ends of the pipes and the pipe connections of the outdoor unit 2 For connection first align the center then tig...

Page 10: ...ure is applied This may cause gas leak Service port Charge hose for R32 R410A Body Close Open Control valve A When attaching the control valve to the service port make sure that the valve core is in closed position and then tighten part A Do not tighten part A or turn the body when valve core is in open position Service port cap Torque 13 7 to 17 7 N m 140 to 180 kgf cm Charge hose for R32 R410A 4...

Page 11: ...e Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant ...

Page 12: ...VG79Y196H02 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y196H02 indd 11 2020 05 27 11 45 09 ...

Reviews: