1-2. SPECIFICATIONS

Model

Power supply *1

Wire specifications *2

Pipe length and height difference *3, *4, *5, 

*6, *7, *8

Rated 

Voltage

Fre-

quency

Breaker 

capacity

Power 
supply

Indoor/outdoor 

connecting wire

Max. pipe 

length per in-
door unit / for 

multi-system

Max. height 

difference *9

Max. no. of 

bends per in-
door unit / for 

multi-system

MXZ-2F52VF

220 V - 60 Hz
230 V - 50 Hz

15 A

3-core 

2.0 mm

2

4-core 

1.0/1.5 mm

2

20 m / 30 m

15 m

20 / 30

 

CAUTION

(Could lead to serious injury in particular environments when operated incorrectly.)

n

  Install an earth leakage breaker depending on the installation place.

 

If an earth leakage breaker is not installed, it could cause electric shock.

n

  Perform the drainage/piping work securely according to the instal-

lation manual.

  If there is defect in the drainage/piping work, water could drop from the 

unit, soaking and damaging household goods.

n

  Do not touch the air inlet or the aluminum fins of the outdoor unit.

 

This could cause injury. 

n

  Do not install the outdoor unit where small animals may live.

  If small animals enter and touch the electric parts inside the unit, it could 

cause a malfunction, smoke emission, or fire. Also, advise user to keep 

the area around the unit clean. 

n

  Do not operate the air conditioner during interior construction and 

finishing work, or while waxing the floor. 

 

Before operating the air conditioner, ventilate the room well after such work 
is performed. Otherwise, it may cause volatile elements to adhere inside 
the air conditioner, resulting in water leakage or scattering of dew.

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

(Unit: mm (inch))

Port size of outdoor unit

Optional different-diameter joints (port size of outdoor unit → diameter of connection pipe)

MXZ-2F

Liquid / Gas

9.52 (3/8) 

 12.7 (1/2) : MAC-A454JP-E

Refer to the installation manual of indoor unit for the diameter of connection pipe of indoor unit.

A , B UNIT

6.35 (1/4) / 9.52 (3/8)

*1  Connect to the power switch which has a gap of 3 mm or more when open to interrupt the 

source power phase. (When the power switch is shut off, it must interrupt all phases.)

*2  Use wires in conformity with design 60245 IEC 57. Use the indoor/outdoor connecting wire in 

conformity with the wire specifications specified in the installation manual of the indoor unit.

*3  Never use pipes with thickness less than specified. The pressure resistance will be insufficient.

*4  Use a copper pipe or a copper-alloy seamless pipe.
*5  Be careful not to crush or bend the pipe during pipe bending.
*6  Refrigerant pipe bending radius must be 100 mm or more.

*7  Insulation material : Heat resisting foam plastic 0.045 specific gravity

*8  Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect 

installation of the indoor unit and insufficient thickness may cause dew drippage.

*9

  If the outdoor unit is installed higher than the indoor unit, max. height difference is reduced 

to 10 m.

1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunshine can be avoided as much as possible.
•  Where neighbours are not annoyed by operation sound or hot air.
•  Where rigid wall or support is available to prevent the increase of opera-

tion sound or vibration.

•  Where there is no risk of combustible gas leakage.
•  When installing the unit, be sure to secure the unit legs.
•  Where it is at least 3 m away from the antenna of TV set or radio. Opera-

tion of the air conditioner may interfere with radio or TV reception in areas 

where reception is weak. An amplifier may be required for the affected 

device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or blowing snow. In 

areas with heavy snow, please install a canopy, a pedestal and/or some 

baffle boards.

Note:

It is advisable to make a piping loop near outdoor unit so as to reduce 
vibration transmitted from there.

Note: 

When operating the air conditioner in low outside temperature, be sure 
to follow the instructions described below.
•  Never install the outdoor unit in a place where its air inlet/outlet side 

may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet 

side facing the wall.

• 

To prevent exposure to wind, it is recommended to install a baffle board 

on the air outlet side of the outdoor unit.

Avoid the following places for installation where air conditioner trouble 
is liable to occur.

•  Where flammable gas could leak.

•  Where there is much machine oil.

•  Where oil is splashed or where the area is filled with oily smoke (such 

as cooking areas and factories, in which the properties of plastic could 
be changed and damaged).

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.
•   Where there is emission of high levels of VOCs, including phthalate 

compounds, formaldehyde, etc., which may cause chemical cracking.

•  The appliance shall be stored so as to prevent mechanical damage 

from occurring.

Model

Maximum amount 

of refrigerant 

charge

Factory-charged 

refrigerant amount

MXZ-2F52VF

1.0 kg

1.0 kg

VG79Y196H02.indd   2

2020/05/27   11:45:06

Summary of Contents for MXZ-2F52VF

Page 1: ...XZ 2F52VF English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit VG79Y196H02 indd 1 2020 05 27 11 45 06 ...

Page 2: ...l cover of the indoor unit and or the service panel of the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc n When installing relocating or servicing the unit make sure that no substance other than the specified refrigerant R32 enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pres sure rise an...

Page 3: ...alloy seamless pipe 5 Be careful not to crush or bend the pipe during pipe bending 6 Refrigerant pipe bending radius must be 100 mm or more 7 Insulation material Heat resisting foam plastic 0 045 specific gravity 8 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage 9 If the o...

Page 4: ... in a sufficiently large space without depressions 1 4 1 Minimum installation area for Outdoor units If you unavoidably install a unit in a space where all four sides are blocked or there are depressions confirm that one of these situations A B or C is satisfied Note These countermeasures are for keeping safety not for specification guarantee A Secure sufficient installation space minimum installa...

Page 5: ... the height from the floor to the bottom of the indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more for floor standing refer to indoor unit Installation manual There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15...

Page 6: ... M kg Amin m 1 00 No requirements 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 84 3 63 1 90 3 75 2 00 3 95 2 10 4 15 2 20 4 34 2 30 4 54 2 40 4 74 h0 Refer to indoor unit installation manual Floor standing VG79Y196H02 indd 5 2020 05 27 11 45 07 ...

Page 7: ...When the piping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for ...

Page 8: ...SE R32 REFRIGERANT Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contaminants...

Page 9: ... Use a joint pipe if the connection of the indoor unit differs Use tightening torque table above as a guideline for indoor unit side union joint section and tighten using two wrenches Excessive tightening dam ages the flare section 1 Apply a thin coat of refrigeration oil G to the flared ends of the pipes and the pipe connections of the outdoor unit 2 For connection first align the center then tig...

Page 10: ...ure is applied This may cause gas leak Service port Charge hose for R32 R410A Body Close Open Control valve A When attaching the control valve to the service port make sure that the valve core is in closed position and then tighten part A Do not tighten part A or turn the body when valve core is in open position Service port cap Torque 13 7 to 17 7 N m 140 to 180 kgf cm Charge hose for R32 R410A 4...

Page 11: ...e Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant ...

Page 12: ...VG79Y196H02 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y196H02 indd 11 2020 05 27 11 45 09 ...

Reviews: