background image

9

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor 

unit gas pipe. (The stop valves are fully closed and covered in caps 
in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of 

stop valve on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)
4) Check the vacuum with gauge manifold valve, then close gauge 

manifold valve, and stop the vacuum pump.

5)  Leave as it is for one or two minutes. Make sure the pointer of gauge 

manifold valve remains in the same position. Confirm that pressure 

gauge shows -0.101 MPa [Gauge] (-760 mmHg).

6)  Remove gauge manifold valve quickly from service port of stop valve.
7) Fully open all stop valves on the gas pipe and the liquid pipe. Oper-

ating without fully opening lowers the performance and this causes 
trouble.

8) Refer to 1-2., and charge the prescribed amount of refrigerant if 

needed. Be sure to charge slowly with liquid refrigerant.

9) Tighten cap of service port to obtain the initial status.
10) Leak  test

Stop valve 
for LIQUID

Stop valve cap 
(Torque 19.6 to 
29.4 N•m, 200 
to 300 kgf•cm)

Gauge manifold 
valve (for R32, 
R410A)

Compound pressure 
gauge (for R32, R410A)

–0.101 MPa  
(–760 mmHg)

Handle 
Low

Handle High

Vacuum pump
(for R32, R410A)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Stop valve 
for GAS

Pressure gauge
(for R32, R410A)

Precautions when using 
the control valve

When attaching the control valve 
to the service port, valve core 
may deform or loosen if excess 
pressure is applied. This may 
cause gas leak.

Service 
port

Charge hose 
(for R32, R410A)

Body

Close

Open

Control 
valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then tighten part A. Do not tighten 
part A or turn the body when valve 
core is in open position.

Service port cap
(Torque 13.7 to 17.7 
N•m, 140 to 180 kgf•cm)

Charge hose (for 
R32, R410A)

4-2. GAS CHARGE

Perform gas charge to unit.
1) Connect gas cylinder to the service port of stop valve.
2)  Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish  specified  amount  of  the  refrigerant,  while  operating  the  air 

conditioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the 

refrigerating cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure 
to use liquid refrigerant. Charge the liquid refrigerant slowly, otherwise the 
compressor will be locked.
To maintain the high pressure of the gas cylinder, warm the gas cylinder 

with warm water (under 40°C) during cold season. But never use naked fire 

or steam.

Refrigerant gas 
cylinder operating 
valve
(for R32, R410A)

Indoor 

unit

Charge hose (for R32, 
R410A)

Refrigerant gas cylinder for 
R32, R410A with siphon

Electronic scale for 
refrigerant charging

Refrigerant (liquid)

Indoor 

unit

Union

Union

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

Stop valve

Service port

Outdoor 

unit

Gauge manifold 
valve (for R32, 
R410A)

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Make sure to replace the 
cap after the operation.

 WARNING

To avoid risk of fire, make sure that there are no flammable 

hazards or ignition risks before opening the stop valves.

<R32>

VG79Y196H02.indd   9

2020/05/27   11:45:09

Summary of Contents for MXZ-2F52VF

Page 1: ...XZ 2F52VF English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit VG79Y196H02 indd 1 2020 05 27 11 45 06 ...

Page 2: ...l cover of the indoor unit and or the service panel of the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc n When installing relocating or servicing the unit make sure that no substance other than the specified refrigerant R32 enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pres sure rise an...

Page 3: ...alloy seamless pipe 5 Be careful not to crush or bend the pipe during pipe bending 6 Refrigerant pipe bending radius must be 100 mm or more 7 Insulation material Heat resisting foam plastic 0 045 specific gravity 8 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage 9 If the o...

Page 4: ... in a sufficiently large space without depressions 1 4 1 Minimum installation area for Outdoor units If you unavoidably install a unit in a space where all four sides are blocked or there are depressions confirm that one of these situations A B or C is satisfied Note These countermeasures are for keeping safety not for specification guarantee A Secure sufficient installation space minimum installa...

Page 5: ... the height from the floor to the bottom of the indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more for floor standing refer to indoor unit Installation manual There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15...

Page 6: ... M kg Amin m 1 00 No requirements 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 84 3 63 1 90 3 75 2 00 3 95 2 10 4 15 2 20 4 34 2 30 4 54 2 40 4 74 h0 Refer to indoor unit installation manual Floor standing VG79Y196H02 indd 5 2020 05 27 11 45 07 ...

Page 7: ...When the piping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for ...

Page 8: ...SE R32 REFRIGERANT Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contaminants...

Page 9: ... Use a joint pipe if the connection of the indoor unit differs Use tightening torque table above as a guideline for indoor unit side union joint section and tighten using two wrenches Excessive tightening dam ages the flare section 1 Apply a thin coat of refrigeration oil G to the flared ends of the pipes and the pipe connections of the outdoor unit 2 For connection first align the center then tig...

Page 10: ...ure is applied This may cause gas leak Service port Charge hose for R32 R410A Body Close Open Control valve A When attaching the control valve to the service port make sure that the valve core is in closed position and then tighten part A Do not tighten part A or turn the body when valve core is in open position Service port cap Torque 13 7 to 17 7 N m 140 to 180 kgf cm Charge hose for R32 R410A 4...

Page 11: ...e Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant ...

Page 12: ...VG79Y196H02 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y196H02 indd 11 2020 05 27 11 45 09 ...

Reviews: