11
7URXEOHVKRRWLQJSURFHGXUH
1) Check if the OPERATION INDICATOR lamp on the indoor unit is blinking on and off to indicate an abnormality. To
make sure, check how many times the OPERATIONAL INDICATOR lamp is blinking on and off before starting service
work.
2) When the outdoor control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
3) When troubleshooting, refer to 11-2, 11-3 and 11-4.
Lead wirin
Connector housin
<Incorrect>
<Correct>
11-1. CAUTIONS ON TROUBLESHOOTING
%HIRUHWURXEOHVKRRWLQJFKHFNWKHIROORZLQJ
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
7DNHFDUHRIWKHIROORZLQJGXULQJVHUYLFLQJ
1) Before servicing the air conditioner, be sure to turn OFF the unit first with the remote controller, and then after confirm-
ing the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the outdoor
control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
TROUBLESHOOTING
11-2. FAILURE MODE RECALL FUNCTION
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-4) disappears, the memorized failure details
can be recalled.
)ORZFKDUWRIIDLOXUHPRGHUHFDOOIXQFWLRQIRUWKHLQGRRURXWGRRUXQLW
Refer to the service manual of indoor unit.
MXZ-2C20NA2
MXZ-3C24NA
MXZ-3C30NA
MXZ-4C36NA
MXZ-5C42NA
MXZ-2C20NAHZ
MXZ-3C24NAHZ
MXZ-3C30NAHZ
MXZ-3C24NA2
MXZ-3C30NA2
MXZ-4C36NA2
MXZ-5C42NA2
MXZ-2C20NAHZ2 MXZ-3C24NAHZ2 MXZ-3C30NAHZ2
OBH702G
Summary of Contents for MXZ-2C20NA2-U1
Page 19: ...19 MXZ 4C36NA MXZ 4C36NA2 Unit inch mm Lock nut Conduit plates Conduit connector OBH702G ...
Page 21: ...21 MXZ 2C20NAHZ MXZ 2C20NAHZ2 Unit inch mm Lock nut Conduit connector Conduit plate OBH702G ...
Page 24: ...24 MXZ 3C24NA MXZ 3C30NA OBH702G ...
Page 25: ...25 MXZ 3C24NA2 MXZ 3C30NA2 OBH702G ...
Page 26: ...26 MXZ 4C36NA OBH702G ...
Page 27: ...27 MXZ 4C36NA2 OBH702G ...
Page 29: ...29 MXZ 5C42NA2 OBH702G ...
Page 30: ...30 MXZ 2C20NAHZ OBH702G ...
Page 31: ...31 MXZ 2C20NAHZ2 OBH702G ...
Page 32: ...32 MXZ 3C24NAHZ MXZ 3C30NAHZ OBH702G ...