41
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Outdoor unit union diameter
For
Indoor unit A
Liquid
1/4
Gas
1/2
Indoor unit B
Liquid
1/4
Gas
3/8
Indoor unit C
Liquid
1/4
Gas
3/8
Indoor unit D
Liquid
1/4
Gas
3/8
Indoor unit E
Liquid
1/4
Gas
3/8
2SHUDWLQJ5DQJH
MXZ-5C42NA MXZ-5C42NA2
Piping length each indoor unit (a, b, c, d, e)
82 ft. MAX.
Total piping length (a+b+c+d+e)
262 ft. MAX.
Bending point for each unit
25 MAX.
Total bending point
80 MAX.
It is irrelevant which unit is higher.
MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION
MXZ-5C42NA MXZ-5C42NA2
Unit: inch
a
b
e
c
d
Outdoor
unit
Indoor
units
49 ft.
49 ft.
49 ft.
Max. height difference
Indoor intake air temperature Outdoor intake air temperature
Cooling
Maximum
95°FDB, 71°FWB
115°FDB
Minimum
67°FDB, 57°FWB
14°FDB
Heating
Maximum
80°FDB, 67°FWB
75°FDB, 65°FWB
Minimum
70°FDB, 60°FWB
6°FDB, 5°FWB
OBH702G
Summary of Contents for MXZ-2C20NA2-U1
Page 19: ...19 MXZ 4C36NA MXZ 4C36NA2 Unit inch mm Lock nut Conduit plates Conduit connector OBH702G ...
Page 21: ...21 MXZ 2C20NAHZ MXZ 2C20NAHZ2 Unit inch mm Lock nut Conduit connector Conduit plate OBH702G ...
Page 24: ...24 MXZ 3C24NA MXZ 3C30NA OBH702G ...
Page 25: ...25 MXZ 3C24NA2 MXZ 3C30NA2 OBH702G ...
Page 26: ...26 MXZ 4C36NA OBH702G ...
Page 27: ...27 MXZ 4C36NA2 OBH702G ...
Page 29: ...29 MXZ 5C42NA2 OBH702G ...
Page 30: ...30 MXZ 2C20NAHZ OBH702G ...
Page 31: ...31 MXZ 2C20NAHZ2 OBH702G ...
Page 32: ...32 MXZ 3C24NAHZ MXZ 3C30NAHZ OBH702G ...