44
Primary current protection
Secondary current protection
High-pressure protection
Defrosting in cooling
3 times
Lighting
Discharge temperature
protection
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6.
D
"Check of LEV".
• Refer to 11-6.
F
"Check of outdoor thermistors".
4 times
Lighting
Low discharge
temperature protection
• Refer to 11-6.
D
"Check of LEV".
• Check refrigerant circuit and refrigerant amount.
5 times
Lighting
Cooling high-pressure
protection
This symptom does not mean any abnormality of the
product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
-
-
These symptoms do not mean any abnormality of the
product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Twice
Lighting
Once
Lighting
When the frequency of the compressor is kept 80Hz or more and
the discharge temperature is kept under 122˚F(COOL mode)
/104˚F(HEAT mode) for more than 40 minutes.
When the frequency of the compressor is kept 80Hz or more and
the discharge temperature is kept under 102.2˚F for more than 20
minutes.
When the outdoor heat exchanger temperature exceeds 136.4˚F
during operation.
9 times
Lighting
Inverter check mode
Lighting
Lighting
Normal
When the unit is operated with emergency operation switch.
-
When the input current exceeds 15A.
When the current of the compressor exceeds 15A.
When the indoor gas pipe temperature exceeds 113˚F during heating.
When the indoor gas pipe temperature falls 37.4˚F or below during cooling.
Outdoor electronic control P.C. board(Parts side)
Lighting
LED2 LED1
LED1(Red) LED2(Yellow)
Abnormal point / Condition
Correspondence
Indication
Condition
Outdoor unit
operates.
Outdoor unit
operates
normally.
No. Symptom
21
22
23
24
25
26
27
ON
OFF
2.5-second OFF
2.5-second OFF
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
0.5-second ON
0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.1.
2. LED is lighted during normal operation.
OB444B--2.qxp 07.4.17 4:33 PM Page 44
Summary of Contents for MXZ-2A20NA-1
Page 15: ...15 WIRING DIAGRAM 6 MXZ 2A20NA OB444B 1 qxp 07 4 17 4 27 PM Page 15 ...
Page 16: ...16 MXZ 2A20NA 1 OB444B 1 qxp 07 4 17 4 28 PM Page 16 ...
Page 17: ...17 MXZ 3A30NA OB444B 1 qxp 07 4 17 4 28 PM Page 17 ...
Page 18: ...18 MXZ 3A30NA 1 OB444B 1 qxp 07 4 17 4 28 PM Page 18 ...