15
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m
Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas
Liquid
MUZ-LN25VGHZ
MUZ-LN35VGHZ
20
12
9.52
6.35
MUZ-LN50VGHZ
30
15
9.52
6.35
ADDITIONAL REFRIGERANT CHARGE (R32: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
11 m
12 m
13 m
14 m
15 m
16 m
17 m
18 m
20 m
MUZ-LN25/35VGHZ
1,000
0
80
100
120
140
160
180
200
220
260
Calculation: X g = 20 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
16 m
17 m
20 m
25 m
30 m
MUZ-LN50VGHZ
1,450
0
180
200
260
360
460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
OBH768