27
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-LN25VGHZ
CAPACITY: 3.2 kW
INPUT: 580 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10
-5
0
5
10
15
20
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
15
2.02
377
2.43
452
2.85
510
3.26
551
3.68
586
4.06
603
4.48
615
21
1.92
406
2.30
481
2.72
534
3.10
574
3.52
603
3.90
621
4.30
644
26
1.73
435
2.14
510
2.53
563
2.94
603
3.36
632
3.74
650
4.16
667
MUZ-LN35VGHZ
CAPACITY: 4.0 kW
INPUT: 800 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10
-5
0
5
10
15
20
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
15
2.52
520
3.04
624
3.56
704
4.08
760
4.60
808
5.08
832
5.60
848
21
2.40
560
2.88
664
3.40
736
3.88
792
4.40
832
4.88
856
5.38
888
26
2.16
600
2.68
704
3.16
776
3.68
832
4.20
872
4.68
896
5.20
920
MUZ-LN50VGHZ
CAPACITY: 6.0 kW
INPUT: 1480 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10
-5
0
5
10
15
20
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
Q
INPUT
15
3.78
962
4.56
1154
5.34
1302
6.12
1406
6.90
1495
7.62
1539
8.40
1569
21
3.60
1036
4.32
1228
5.10
1362
5.82
1465
6.60
1539
7.32
1584
8.07
1643
26
3.24
1110
4.02
1302
4.74
1436
5.52
1539
6.30
1613
7.02
1658
7.80
1702
NOTE:
Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
OBH768