J Check of power supply
Is there voltage 230VAC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If lights up, OK.
If
fl
ashes, refer to 12-3.
Does POWER lamp on the indoor
unit light up?
Does LED on the inverter P.C.
board light up or
fl
ash?
(Refer to 12-6.1.)
No
Replace the inverter
P.C. board.
Is there bus-bar voltage 260 - 370V
DC between DB61 (+) and DB61 (–)
(
MUZ-LN25/35VGHZ
)/325 - 370VDC
between IC700 (P) and (N)
(
MUZ-LN50VGHZ
) on the inverter P.C.
board? (Refer to 12-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between the
compressor and the power module
(IC700). Turn ON power supply and
press EMERGENCY OPERATION
switch.
Inverter P.C. board
(Solder side)
DB61
260 - 370VDC
MUZ-LN25/35VGHZ
325 -370VDC
MUZ-LN50VGHZ