35
MUZ-FD50VABH
Part name
Check method and criterion
Figure
Defrost thermistor (RT61)
Fin temperature thermistor
(RT64)
Ambient temperature ther-
mistor (RT65)
Outdoor heat exchanger tem-
perature thermistor (RT68)
Measure the resistance with a tester.
Refer to 11-6. "Test point diagram and voltage", 2. "Outdoor elec-
tronic control P.C. board”, the chart of thermistor.
Discharge temperature
thermistor (RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. "Test point diagram and voltage", 2. "Outdoor elec-
tronic control P.C. board", the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester.
(Winding temperature : -20 ~ 40°C)
Normal
0.57 ~ 0.82
Ω
Outdoor fan motor
Measure the resistance between lead wires using a tester.
(Part temperature : -20 ~ 40°C)
Color of lead wire
Normal
RED – BLK
12 ~ 17
Ω
BLK – WHT
WHT – RED
R. V. coil
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Normal
1.15 ~ 1.71 k
Ω
Linear expansion valve
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Color of lead wire
Normal
WHT – RED
37 ~ 54
Ω
RED – ORN
YLW – BRN
BRN – BLU
High pressure switch
(HPS)
Pressure
3.7 ± 0.15 MPa
Close
4.8
+0.05
-0.1
MPa
Open
Defrost heater
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Normal
349 ~ 428
Ω
W
U
V
WHT
RED
BLK
LEV
WHT
RED
YLW BRN
ORN
BLU
U
RED
WHT
BLK
V
W
(W)
(V)
(U)