ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
5 m
6 m
7 m
8 m
9 m
10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-FD25
MUZ-FD35
1,150
0
0
0
90
120
150
180
210
240
270
300
450
Calculation : X g = 30 g/m × (Refrigerant piping length (m) - 5)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
10 m
15 m
20 m
25 m
30 m
MUZ-FD50
1,550
0
90
240
390
540
690
Calculation : X g = 30 g/m × (Refrigerant piping length (m) - 7)
NOTE
: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping : m
Piping size O.D : mm
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-FD25
MUZ-FD35
20
12
9.52
6.35
MUZ-FD50
30
15
12.7