34
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-FD25VABH MUZ-FD35VABH
Part name
Check method and criterion
Figure
Defrost thermistor (RT61)
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger
temperature thermistor
(RT68)
Measure the resistance with a tester.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, the chart of thermistor.
Discharge temperature
thermistor (RT62)
Fin temperature
thermistor (RT64)
Measure the resistance with a tester. Before measurement, hold the
thermistor with your hands to warm it up.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester.
(Winding temperature : -20 ~ 40°C)
Normal
U-V
U-W
V-W
0.78 ~ 1.11
Ω
Outdoor fan motor
Measure the resistance between lead wires using a tester.
(Part temperature : -20 ~ 40°C)
Color of lead wire
Normal
RED – BLK
BLK – WHT
WHT – RED
11 ~ 16
Ω
R. V. coil (21S4)
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Normal
1.19 ~ 1.78 k
Ω
Expansion valve coil
(LEV)
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Color of lead wire
Normal
WHT – RED
37 ~ 54
Ω
RED – ORN
YLW – BRN
BRN – BLU
Defrost heater
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Normal
349 ~ 428
Ω
2
3
W
U
V
1
WHT
RED BLK
2
3
W
U
V
1
WHT
RED BLK
LEV
WHT
RED
ORN
YL
W
BRN
BLU
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy