3
SPECIFICATION
3
Outdoor model
MUH-GD80VB
Function
Cooling
Heating
Power supply
Single phase
230 V, 50 Hz
Capacity
kW
8.0
9.4
Electrical
data
Breaker capacity
A
25
Running current (Total)
A
14.76
15.90
Power input (Total)
W
3,320
3,580
Power factor (Total)
%
98
Starting current (Total)
A
90
Coeffi cient of performance (C.O.P) (Total)
2.41
2.63
Compressor
Model
NN37VAAHT
Output
W
2,500
Compressor motor current
A
13.85
14.62
Fan
motor
Model
RA6V75-AD
Fan motor current
A
0.57
Dimensions W H D
mm
840 850 330
Weight
kg
77
Special
remarks
Dehumidifi cation
/h
4.6
-
Air fl ow (High/Low)
/h
2,940/1,470
Sound level (High/Low)
dB
55/53
Fan speed (High/Low)
rpm
805/435
Fan speed regulator
2
Refrigerant fi lling
capacity (R410A)
kg
2.40
Refrigeration oil (Model)
NEO 22
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor
Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C
Heating: Indoor
Dry-bulb temperature 20°C Wet-bulb temperature 15.5°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Indoor-Outdoor piping length: 5 m
90
80
70
60
50
40
30
20
10
63
125
250
500
1000
2000
4000
8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
55
SPL(dB(A))
LINE
High
FAN SPEED
Test conditions,
Cooling : Dry-bulb temperature 35 Wet-bulb temperature 24
Heating : Dry-bulb temperature 7 Wet-bulb temperature 6
OCT
A
VE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE CRITERIA CURVES
4
MUH-GD80VB
OUTDOOR UNIT
MICROPHONE
1m