HFC
utilized
R410A
INDOOR UNIT
SERVICE MANUAL
No. OBH733
REVISED EDITION-J
Indoor unit service manual
MSZ-GL•NA, MSY-GL•NA Series (OBH732)
MUZ-GL18/24NA
MUZ-GL18/24NAH
MUY-GL18/24NA
PARTS CATALOG (OBB733)
OBH733 REVISED EDITION-H is void.
Revision J:
• A warning when opening or closing the valve has
been added.
CONTENTS
1. TECHNICAL CHANGES ······························3
2. PART NAMES AND FUNCTIONS ··················3
3. SPECIFICATION ········································4
4. OUTLINES AND DIMENSIONS ·····················7
5. WIRING DIAGRAM ·····································9
6. REFRIGERANT SYSTEM DIAGRAM ··········· 21
7. DATA······················································ 24
8. ACTUATOR CONTROL ····························· 39
9. SERVICE FUNCTIONS ······························ 40
10. TROUBLESHOOTING ······························· 41
11. DISASSEMBLY INSTRUCTIONS ················· 65
OUTDOOR UNIT
Models
MUZ-GL09NA -
U1
,
U2
,
U8
MUZ-GL09NAH -
U1
,
U2
,
U8
MUY-GL09NA -
U1
,
U2
MUZ-GL12NA -
U1
,
U2
MUZ-GL12NAH -
U1
,
U2
MUY-GL12NA -
U1
,
U2
MUZ-GL15NA -
U1
,
U2
MUZ-GL15NAH -
U1
,
U2
MUY-GL15NA -
U1
,
U2
MUZ-GL18NA -
U1
MUZ-GL18NAH -
U1
MUY-GL18NA -
U1
MUZ-GL24NA -
U1
,
U2
MUZ-GL24NAH -
U1
MUY-GL24NA -
U1
Summary of Contents for MSY-GL-NA Series
Page 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733J ...
Page 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733J ...
Page 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733J ...
Page 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733J ...
Page 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733J ...
Page 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733J ...
Page 15: ...15 MUZ GL18NA OBH733J ...
Page 16: ...16 MUZ GL18NAH OBH733J ...
Page 17: ...17 MUY GL18NA OBH733J ...
Page 18: ...18 MUZ GL24NA OBH733J ...
Page 19: ...19 MUZ GL24NAH OBH733J ...
Page 20: ...20 MUY GL24NA OBH733J ...
Page 75: ...75 OBH733J ...