19
Indoor
unit
w
Max. Height
difference 5m
(MS-18/24RV)
/15m(MS-30RV)
w
Height difference should be within 5m(MS-18/24RV) /15m(MS-30RV)
regardless of which unit, indoor or outdoor position is high.
Outdoor unit
Refrigerant Piping
Max.length
A
Model
Outdoor unit precharged
1,050
2,150
Refrigerant piping length (one way)
15m
120
7m
0
10m
45
MS-18RV -
E1
MU-18RV -
E1
MS-24RV -
E1
MU-24RV -
E1
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R22 : g)
Model
Refrigerant piping
Max. length : m
A
Piping size O.D : mm
Length of connecting pipe : m
Indoor unit
Gas 0.43
Liquid 0.5
Gas
15.88
Liquid
6.35
9.52
Outdoor unit
Gas 0
Liquid 0
MS-18RV -
E1
MU-18RV -
E1
MS-24RV -
E1
MU-24RV -
E1
15
30
MS-30RV -
E1
MU-30RV -
E1
MAX. REFRIGERANT PIPING LENGTH
Calculation : Xg=15g/mx(Refrigerant piping length (m)-7)
Outdoor unit
precharged
0
45
120
Refrigerant piping length (one way)
15m
10m
7m
Model
2,400
20m
25m
30m
195
345
270
MS-30RV -
E1
MU-30RV -
E1
Calculation : Xg=15g/m
o
(Refrigerant piping length(m)-7)