Mitsubishi Electric Mr.Slim SUZ-KA25VA5 Installation Manual Download Page 8

8

When relocating or disposing of the air conditioner, pump down the system following 

the procedure below so that no refrigerant is released into the atmosphere.

1

  Turn off the power supply (circuit breaker).

2

  Connect the gauge manifold valve to the service port of the stop valve on the gas 

pipe side of the outdoor unit.

3

  Fully close the stop valve on the liquid pipe side of the outdoor unit.

4

  Supply power (circuit breaker).

 

5

 Perform the refrigerant collecting operation (cooling test run).

 

• 

  For the PAR-31MAA, select “Service” → “TestRun” from the main menu to start 

the test run, and then select the cooling mode.

 

• 

  For details or for other information about starting the test run when using re-
mote controllers, refer to the installation manual for the indoor unit or the re-
mote controller.

6

  Fully close the stop valve on the gas pipe side of the outdoor unit when the pres-

sure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

) and quickly 

stop the air conditioner.

 

• 

 Push the “ON/OFF” button on the remote controller to stop the air conditioner.

  *   Note  that  when  the  extension  piping  is  very  long  with  a  large  refrigerant 

amount, it may not be possible to perform a pump-down operation. In this case, 
use refrigerant recovery equipment to collect all of the refrigerant in the system.

7

  Turn off the power supply (circuit breaker), remove the gauge manifold valve, and 

then disconnect the refrigerant pipes.

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes.

•  If the refrigerant pipes are disconnected while the compressor is operating 

and the stop valve (ball valve) is open, the pressure in the refrigeration cycle 

could become extremely high if air is drawn in, causing the pipes to burst, 

personal injury, etc.

8. Pumping down

Outdoor model

SUZ-KA25VA5.TH

SUZ-KA35VA5.TH

SUZ-KA50VA5.TH

SUZ-KA60VA5.TH

SUZ-KA71VA5.TH

Power supply

Single phase 230 V, 50 Hz

Dimensions W × H × D

mm

800 × 550 × 285

840 × 880 × 330

Weight

kg

30

35

54

50

53

Sound level *1

Cooling 

dB (A)

47

49

52

55

Heating

48

50

52

55

*1  Measured under rated operating frequency.

9. Specifications

01_RG79Y757H01_EN.indd   8

7/23/2015   3:48:01 PM

Summary of Contents for Mr.Slim SUZ-KA25VA5

Page 1: ...ente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδ...

Page 2: ...hen installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refr...

Page 3: ...stall the outdoor unit with its air inlet side facing the wall To prevent exposure to wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Units should be installed by licensed contractor accordingly to local code re quirement Fig 4 1 4 Drain piping for outdoor unit Fig 4 1 4 1 Accessories Check the following parts before installation Outdoor unit 1 Drain soc...

Page 4: ...KA60 For liquid 6 35 1 4 0 8 mm 8 mm For gas 15 88 5 8 0 8 mm 8 mm SUZ KA71 For liquid 9 52 3 8 0 8 mm 8 mm For gas 15 88 5 8 1 0 mm 8 mm 2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation 3 Refrigerant pipe bending radius must be 100 mm or more Caution Using careful insulation of specified thickness Excessive thickness prevents storage behind the indoor unit and smal...

Page 5: ...een the indoor and the outdoor units After refrigerant pipes are connected and evacuated fully open all stop valves on gas and liquid pipe sides Operating without fully opening lowers the performance and causes trouble Pipe length 7 m maximum No gas charge is needed Pipe length exceeding 7 m Charge the prescribed amount of gas Remove the service port cap of the stop valve on the side of the outdoo...

Page 6: ...n terminal screws securely Wiring should be done so that the power lines are not subject to tension Otherwise heat may be generated or fire may occur A B C D S3 S3 S2 S1 1 S 2 S L N 2 1 E B C L N A E D C Fig 6 1 Fig 6 2 Fig 6 4 A Indoor unit B Outdoor unit C Wired main switch Earth leakage breaker D Earth E Remote controller For Power supply Indoor terminal block Earth wire green yellow Indoor out...

Page 7: ...or unit Outdoor unit S1 S2 2 230 VAC 230 VAC 230 VAC Indoor unit Outdoor unit S2 S3 2 12 VDC 24 VDC 12 VDC 24 VDC 12 VDC 24 VDC 1 A breaker with at least 3 mm contact separation in each poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics ...

Page 8: ...stop the air conditioner Push the ON OFF button on the remote controller to stop the air conditioner Note that when the extension piping is very long with a large refrigerant amount it may not be possible to perform a pump down operation In this case use refrigerant recovery equipment to collect all of the refrigerant in the system 7 Turn off the power supply circuit breaker remove the gauge manif...

Page 9: ...r for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer MITSUBISHI ELECTRIC SUZ KA25VA SUZ KA35VA SUZ KA50VA SUZ KA60VA SUZ KA71VA 1 2 3 9 Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remarque Le numéro de série de l appareil se trouve sur la plaque du produit O...

Page 10: ... brännskador eller köldskador Stoppa aldrig batterier i munnen de kan sväljas av misstag Om ett batteri sväljs kan det leda till kvävning och eller förgiftning Montera enheten på ett stadigt underlag för att förhindra höga driftljud och vibrationer Ljudmätningar har utförts i enlighet med JIS C9612 JIS B8616 ISO 5151 T1 och ISO 13523 T1 NEDERLANDS Het Engels is het origineel De andere taalversies ...

Page 11: ... address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC RoHS Directive 2011 65 EU Energy relate...

Reviews: