1. The following should always be observed for safety

• 

After reading this manual, be sure to keep it together with the instruction 
manual in a handy place on the customer’s site.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

•   Do not install it by yourself (customer).

Incomplete installation could cause injury due to fire, electric shock, the 

unit falling or leakage of water. Consult the dealer from whom you pur-
chased the unit or special installer.

•   This appliance is intended to be used by expert or trained users in shops, in 

light industry and on farms, or for commercial use by lay persons.

•   Install the unit securely in a place which can bear the weight of the unit.

When installed in an insufficient strong place, the unit could fall causing 

injured.

•   Use the specified wires to connect the indoor and outdoor units securely 

and attach the wires firmly to the terminal board connecting sections so the 

stress of the wires is not applied to the sections.

Incomplete connecting and fixing could cause fire.

•   Do not use intermediate connection of the power cord or the extension cord 

and do not connect many devices to one AC outlet.

It could cause a fire or an electric shock due to defective contact, defective 

insulation, exceeding the permissible current, etc.

•   

Check that the refrigerant gas does not leak after installation has completed.

•   Perform the installation securely referring to the installation manual.

Incomplete installation could cause a personal injury due to fire, electric 

shock, the unit falling or leakage of water.

•   Use only specified cables for wiring. The wiring connections must be made 

securely with no tension applied on the terminal connections. Also, never 

splice the cables for wiring (unless otherwise indicated in this document).

  Failure to observe these instructions may result in overheating or a fire.

•   Perform electrical work according to the installation manual and be sure to 

use an exclusive circuit.

If the capacity of the power circuit is insufficient or there is incomplete elec

-

trical work, it could result in a fire or an electric shock.

•   Attach the electrical part cover to the indoor unit and the service panel to 

the outdoor unit securely.
If the electrical part cover in the indoor unit and/or the service panel in the 

outdoor unit are not attached securely, it could result in a fire or an electric 

shock due to dust, water, etc.

•   Be sure to use the part provided or specified parts for the installation work.

The use of defective parts could cause an injury or leakage of water due to 

a fire, an electric shock, the unit falling, etc.

•   Ventilate the room if refrigerant leaks during operation.

If the refrigerant comes in contact with a flame, poisonous gases will be 

released.

•   

When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes. The compressor may burst if air etc. get into it.

•   When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it 

with any other refrigerant and do not allow air to remain in the lines.

   If air is mixed with the refrigerant, then it can be the cause of abnormal high 

pressure in the refrigerant line, and may result in an explosion and other 

hazards.

   The use of any refrigerant other than that specified for the system will cause 

mechanical failure or system malfunction or unit breakdown. In the worst 
case, this could lead to a serious impediment to securing product safety.

 Caution:

•   Perform grounding.

Do not connect the ground wire to a gas pipe, water pipe arrester or tel-
ephone ground wire. Defective grounding could cause an electric shock.

•   Do not install the unit in a place where an inflammable gas leaks.

If gas leaks and accumulates in the area surrounding the unit, it could cause 

an explosion.

•   Install a ground leakage breaker depending on the installation place (where 

it is humid).

•   Please provide an exclusive circuit for the air conditioner and do not con

-

nect other electrical appliances to it.

•   Be sure to read “The following should always be observed for safety” be

-

fore installing the air conditioner.

•   Be sure to observe the cautions specified here as they include important 

items related to safety.

•   

The indications and meanings are as follows.

 Warning:

Could lead to death, serious injury, etc.

 Caution:

Could lead to serious injury in particular environments when operated incor-
rectly.

If a ground leakage breaker is not installed, it could cause an electric shock.

•   Perform  the  drainage/piping  work  securely  according  to  the  installation 

manual.
If there is a defect in the drainage/piping work, water could drop from the 
unit and household goods could be wet and damaged.

•   Fasten a flare nut with a torque wrench as specified in this manual.

When  fastened  too  tight,  a  flare  nut  may  broken  after  a  long  period  and 

cause a leakage of refrigerant.

2.1. Outdoor unit

•   Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where it is not exposed to rain and direct sunshine.

•  Where neighbours are not annoyed by operation sound or hot air.

•  Where rigid wall or support is available to prevent the increase of operation sound 

or vibration.

•  Where there is no risk of combustible gas leakage.

•  When installing the unit at a high level, be sure to fix the unit legs.

•  Where it is at least 3 m away from the antenna of TV set or radio. (Otherwise, 

images would be disturbed or noise would be generated.)

•  Please install it in an area not affected by snowfall or blowing snow. In areas with 

heavy snow, please install a canopy, a pedestal and/or some baffle boards.

•  Install the unit horizontally.

 Caution:

Avoid the following places for installation where air conditioner trouble is li-
able to occur.

•  Where there is too much machine oil.

•  Salty environment as seaside areas.

•  Hot-spring areas.

•  Where sulfide gas exists.

•  Other special atmospheric areas.

The outdoor unit produces condensate during the heating operation. Select 
the installation place to ensure to prevent the outdoor unit and/or the grounds 
from being wet by drain water or damaged by frozen drain water.

2. Selecting the installation location

6. Electrical work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
7. Maintenance   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
8. Pumping down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

9. Specifications

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

01_RG79Y757H01_EN.indd   2

7/23/2015   3:47:59 PM

Summary of Contents for Mr.Slim SUZ-KA25VA5

Page 1: ...ente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδ...

Page 2: ...hen installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refr...

Page 3: ...stall the outdoor unit with its air inlet side facing the wall To prevent exposure to wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Units should be installed by licensed contractor accordingly to local code re quirement Fig 4 1 4 Drain piping for outdoor unit Fig 4 1 4 1 Accessories Check the following parts before installation Outdoor unit 1 Drain soc...

Page 4: ...KA60 For liquid 6 35 1 4 0 8 mm 8 mm For gas 15 88 5 8 0 8 mm 8 mm SUZ KA71 For liquid 9 52 3 8 0 8 mm 8 mm For gas 15 88 5 8 1 0 mm 8 mm 2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation 3 Refrigerant pipe bending radius must be 100 mm or more Caution Using careful insulation of specified thickness Excessive thickness prevents storage behind the indoor unit and smal...

Page 5: ...een the indoor and the outdoor units After refrigerant pipes are connected and evacuated fully open all stop valves on gas and liquid pipe sides Operating without fully opening lowers the performance and causes trouble Pipe length 7 m maximum No gas charge is needed Pipe length exceeding 7 m Charge the prescribed amount of gas Remove the service port cap of the stop valve on the side of the outdoo...

Page 6: ...n terminal screws securely Wiring should be done so that the power lines are not subject to tension Otherwise heat may be generated or fire may occur A B C D S3 S3 S2 S1 1 S 2 S L N 2 1 E B C L N A E D C Fig 6 1 Fig 6 2 Fig 6 4 A Indoor unit B Outdoor unit C Wired main switch Earth leakage breaker D Earth E Remote controller For Power supply Indoor terminal block Earth wire green yellow Indoor out...

Page 7: ...or unit Outdoor unit S1 S2 2 230 VAC 230 VAC 230 VAC Indoor unit Outdoor unit S2 S3 2 12 VDC 24 VDC 12 VDC 24 VDC 12 VDC 24 VDC 1 A breaker with at least 3 mm contact separation in each poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics ...

Page 8: ...stop the air conditioner Push the ON OFF button on the remote controller to stop the air conditioner Note that when the extension piping is very long with a large refrigerant amount it may not be possible to perform a pump down operation In this case use refrigerant recovery equipment to collect all of the refrigerant in the system 7 Turn off the power supply circuit breaker remove the gauge manif...

Page 9: ...r for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer MITSUBISHI ELECTRIC SUZ KA25VA SUZ KA35VA SUZ KA50VA SUZ KA60VA SUZ KA71VA 1 2 3 9 Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remarque Le numéro de série de l appareil se trouve sur la plaque du produit O...

Page 10: ... brännskador eller köldskador Stoppa aldrig batterier i munnen de kan sväljas av misstag Om ett batteri sväljs kan det leda till kvävning och eller förgiftning Montera enheten på ett stadigt underlag för att förhindra höga driftljud och vibrationer Ljudmätningar har utförts i enlighet med JIS C9612 JIS B8616 ISO 5151 T1 och ISO 13523 T1 NEDERLANDS Het Engels is het origineel De andere taalversies ...

Page 11: ... address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC RoHS Directive 2011 65 EU Energy relate...

Reviews: