Mitsubishi Electric Mr. Slim SUZ-KA25 Installation Instructions Manual Download Page 7

7

S1

S2

S3

S1

S2

S3

6. Electrical work

7. Maintenance

7.1. Gas charge (Fig. 7-1)

1.  Connect gas cylinder to the service port of stop valve (3-way).
2.  Execute air purge of the pipe (or hose) coming from refrigerant gas cylinder.
3.  Replenish specified amount of refrigerant, while running the air condi-

tioner for cooling.

Note:
In case of adding refrigerant, comply with the quantity specifi ed for the refrig-
erating cycle.

 Caution:

•  Do not discharge the refrigerant into the atmosphere.

Take care not to discharge refrigerant into the atmosphere during installa-
tion, reinstallation, or repairs to the refrigerant circuit.

•  For additional charging, charge the refrigerant from liquid phase of the gas 

cylinder.

  If the refrigerant is charged from the gas phase, composition change may 

occur in the refrigerant inside the cylinder and the outdoor unit. In this 
case, ability of the refrigerating cycle decreases or normal operation can 
be impossible. However, charging the liquid refrigerant all at once may 
cause the compressor to be locked. Thus, charge the refrigerant slowly.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm 
water (under 40°C) during cold season. But never use naked fi re or steam.

6.2. Field electrical wiring

Outdoor unit model

SUZ-KA25/KA35

SUZ-KA35 *3

SUZ-KA50/KA60/KA71

Outdoor unit power supply

~/N (single), 50 Hz, 230 V

~/N (single), 50 Hz, 230 V

~/N (single), 50 Hz, 230 V

Outdoor unit input capacity Main switch (Breaker)

*1

10 A

16 A

20 A

Wiring 

Wire No. × 

size (mm

2

)

Outdoor unit power supply

2 × Min. 1.5

2 × Min. 2.0

2 × Min. 2.5

Outdoor unit power supply earth

1 × Min. 1.5

1 × Min. 2.0

1 × Min. 2.5

Indoor unit-Outdoor unit

3 × 1.5 (Polar)

3 × 1.5 (Polar)

3 × 1.5 (Polar)

Indoor unit-Outdoor unit earth

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

Circuit

 rating

Outdoor unit L-N

*2

AC 230 V

AC 230 V

AC 230 V

Indoor unit-Outdoor unit S1-S2

*2

AC 230 V

AC 230 V

AC 230 V

Indoor unit-Outdoor unit S2-S3

*2

DC 12 V ~ DC 24 V

DC 12 V ~ DC 24 V

DC 12 V ~ DC 24 V

*1.  A breaker with at least 3 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
*2. The fi gures are NOT always against the ground.

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.

*3.  In case of PEAD-RP35JA series combination.

Notes: 1. Wiring size must comply with the applicable local and national code.

2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed fl exible cord. (Design 60245 IEC 57)
3. Install an earth longer than other cables.

Outdoor Unit

3 poles isolator

230 V

Single phase

Isolator

Indoor Unit

 Warning:

There is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication 
signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator 
should be used between indoor unit and outdoor unit, please use 3-poles type.

A

 Indoor unit

H

 Refrigerant gas cylinder for R410A with siphon

B

 Union

I

 Refrigerant (liquid)

C

 Liquid pipe

J

 Electronic scale for refrigerant charging

D

 Gas pipe

K

 Charge hose (for R410A)

E

 Stop valve

L

 Gauge manifold valve (for R410A)

F

 Outdoor unit

M

 Service port

G

 Refrigerant gas cylinder 

operating valve

 


Fig. 7-1

Summary of Contents for Mr. Slim SUZ-KA25

Page 1: ...het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condiz...

Page 2: ...ing down the refrigerant stop the compressor before discon necting the refrigerant pipes The compressor may burst if air etc get into it Caution Perform grounding Do not connect the ground wire to a gas pipe water pipe arrester or tele phone ground wire Defective grounding could cause an electric shock Do not install the unit in a place where an inflammable gas leaks If gas leaks and accumulates i...

Page 3: ...air inlet side facing the wall To prevent exposure to wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Units should be installed by licensed contractor accordingly to local code re quirement SUZ KA50 KA60VA2 Air outlet 2 10 mm 21 mm slot Air inlet 285 40 344 5 304 325 800 500 150 400 44 Drainage hole W42 In case of Heater models W33 69 Drain hose Drain so...

Page 4: ...1 4 0 8 mm 8 mm For gas 12 7 1 2 0 8 mm 8 mm SUZ KA60 For liquid 6 35 1 4 0 8 mm 8 mm For gas 15 88 5 8 0 8 mm 8 mm SUZ KA71 For liquid 9 52 3 8 0 8 mm 8 mm For gas 15 88 5 8 1 0 mm 8 mm 2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation 3 Refrigerant pipe bending radius must be 100 mm or more Caution Using careful insulation of specified thickness Excessive thickness...

Page 5: ...r the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R410A 0 101 MPa 760 mmHg Handle Low Handle High Window Charge hose for R410A Vacuum pump Adapter for preventing the back flow Charge hose for R410A Service port Stop valve PURGING PROCEDURES Connect the refrigerant pipes both the liquid and gas pipes betw...

Page 6: ...er than other cables E Power supply cord Caution Use care not to make miswiring Firmly tighten the terminal screws to prevent then from loosening After tightening pull the wires lightly to confirm that they do not move Connect cable from the indoor unit correctly on the terminal block Use the same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra leng...

Page 7: ...1 Min 1 5 1 Min 2 0 1 Min 2 5 Indoor unit Outdoor unit 3 1 5 Polar 3 1 5 Polar 3 1 5 Polar Indoor unit Outdoor unit earth 1 Min 1 5 1 Min 1 5 1 Min 1 5 Circuit rating Outdoor unit L N 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S1 S2 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S2 S3 2 DC 12 V DC 24 V DC 12 V DC 24 V DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separat...

Page 8: ... RG79D664H01 Printed in Thailand Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Reviews: