Mitsubishi Electric Mr. Slim SUZ-KA25 Installation Instructions Manual Download Page 6

6

S3

S3

S2

S1

1

S

2

S

L N

2

1

L N

6. Electrical work

Fig. 6-1

Fig. 6-2

Fig. 6-3

Fig. 6-4

6.1. Outdoor unit (Fig. 6-1, Fig. 6-2, Fig. 6-3, Fig. 6-4)

1

  Remove the service panel.

2

  Wire the cables referring to the Fig. 6-1, Fig. 6-2, Fig. 6-3 and the Fig. 6-4.

A

 Indoor unit

B

 Outdoor unit

C

 Wired main switch/fuse

D

 Grounding

For Power supply

Indoor terminal block

Earth wire (green/yellow)

Indoor/outdoor unit connecting wire
3-core 1.5 mm² or more

Outdoor terminal block

Power supply cord SUZ-KA25/KA35: 1.5 mm² or more

SUZ-KA50/KA60/KA71: 2.5  mm² or more

Service panel

Remove fi xing 
screw to open the 
service panel.

Be sure to fi x the 
indoor/outdoor unit 
connecting wire us-
ing this cord clamp.

A

 Loosen terminal screw

B

 Terminal block

C

 Lead wire

•  Perform wiring as shown in the diagram to the lower left. (Procure the cable locally) 

(Fig. 6-2)
Make sure to use cables of the correct polarity only.

A

 Connecting cable

B

 Indoor terminal block

C

 Outdoor terminal block

D

 Always install an earth wire longer than other cables.

E

 Power supply cord

 Caution:

•  Use care not to make miswiring.
•  Firmly tighten the terminal screws to prevent then from loosening.
•  After tightening, pull the wires lightly to confi rm that they do not move.

•  Connect cable from the indoor unit correctly on the terminal-block.
•  Use the same terminal block and polarity as is used with the indoor unit.
•  For aftercare maintenance, give extra length to connecting cable.

• Both end of connecting cable (extension wire) are peeled off. When too 

long, or connected by cutting off the middle, peel off power supply cable to 
the size given in the fi gure.

•  Be careful not to contact connecting cable with piping.

 Caution:

•  Use care not to make miswiring. (Fig. 6-4)
•  Firmly tighten the terminal screws to prevent them from loosening.
•  After tightening, pull the wires lightly to confi rm that they do not move.

 Warning:

•  Be sure to attach the service panel of the outdoor unit securely. If it is not 

attached correctly, it could result in a fi re or an electric shock due to dust, 
water, etc.

•  Tighten terminal screws securely.
•  Wiring should be done so that the power lines are not subject to tension. 

Otherwise, heat may be generated or fi re may occur.

Summary of Contents for Mr. Slim SUZ-KA25

Page 1: ...het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condiz...

Page 2: ...ing down the refrigerant stop the compressor before discon necting the refrigerant pipes The compressor may burst if air etc get into it Caution Perform grounding Do not connect the ground wire to a gas pipe water pipe arrester or tele phone ground wire Defective grounding could cause an electric shock Do not install the unit in a place where an inflammable gas leaks If gas leaks and accumulates i...

Page 3: ...air inlet side facing the wall To prevent exposure to wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Units should be installed by licensed contractor accordingly to local code re quirement SUZ KA50 KA60VA2 Air outlet 2 10 mm 21 mm slot Air inlet 285 40 344 5 304 325 800 500 150 400 44 Drainage hole W42 In case of Heater models W33 69 Drain hose Drain so...

Page 4: ...1 4 0 8 mm 8 mm For gas 12 7 1 2 0 8 mm 8 mm SUZ KA60 For liquid 6 35 1 4 0 8 mm 8 mm For gas 15 88 5 8 0 8 mm 8 mm SUZ KA71 For liquid 9 52 3 8 0 8 mm 8 mm For gas 15 88 5 8 1 0 mm 8 mm 2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation 3 Refrigerant pipe bending radius must be 100 mm or more Caution Using careful insulation of specified thickness Excessive thickness...

Page 5: ...r the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R410A 0 101 MPa 760 mmHg Handle Low Handle High Window Charge hose for R410A Vacuum pump Adapter for preventing the back flow Charge hose for R410A Service port Stop valve PURGING PROCEDURES Connect the refrigerant pipes both the liquid and gas pipes betw...

Page 6: ...er than other cables E Power supply cord Caution Use care not to make miswiring Firmly tighten the terminal screws to prevent then from loosening After tightening pull the wires lightly to confirm that they do not move Connect cable from the indoor unit correctly on the terminal block Use the same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra leng...

Page 7: ...1 Min 1 5 1 Min 2 0 1 Min 2 5 Indoor unit Outdoor unit 3 1 5 Polar 3 1 5 Polar 3 1 5 Polar Indoor unit Outdoor unit earth 1 Min 1 5 1 Min 1 5 1 Min 1 5 Circuit rating Outdoor unit L N 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S1 S2 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S2 S3 2 DC 12 V DC 24 V DC 12 V DC 24 V DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separat...

Page 8: ... RG79D664H01 Printed in Thailand Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Reviews: