5. Refrigerant piping work

5.2.5. Check (Fig. 5-7)

• Compare 

the 

fl ared work with a fi gure in right side hand.

•  If fl are is noted to be defective, cut off the fl ared section and do fl aring work again.

a

 Smooth all around

f

 Scratch on fl ared plane

b

 Inside is shining without any scratches

g

 Cracked

c

 Even length all around

h

 Uneven

d

 Too much

i

 Bad examples

e

 Tilted

•  Apply a thin coat of refrigeration oil on the seat surface of pipe. (Fig. 5-8)
•  For connection fi rst align the center, then tighten the fi rst 3 to 4 turns of fl are nut.
•  Use tightening torque table below as a guideline for indoor unit side union joint 

section, and tighten using two wrenches. Excessive tightening damages the fl are 
section.

Copper pipe O.D.

(mm)

Flare nut O.D.

(mm)

Tightening torque

(N·m)

ø6.35

17

14 - 18

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø15.88

29

68 - 82

 Warning:

When installing the unit, securely connect the refrigerant pipes before start-
ing the compressor.

 Warning:

Be careful of fl ying fl are nut! (Internally pressurized)
Remove the fl are nut as follows:
1.  Loosen the nut until you hear a hissing noise.
2. Do not remove the nut until the gas has been completely released (i.e., 

hissing noise stops).

3.  Check that the gas has been completely released, and then remove the nut.

Fig. 5-7

Fig. 5-8

1

0

/

2

3

4

5

6

7

B

5.5. Purging procedures leak test

*Close

*Open

Hexagonal wrench

Stop valve

*4 to 5 turns

Stop valve

(or the vacuum
pump with the
function to
prevent the back
flow)

Gauge manifold
valve (for R410A)

Pressure gauge

  (for R410A)

Compound pressure
gauge (for R410A)

-0.101 MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose
(for R410A)

Vacuum

pump

Adapter for
preventing
the back flow

Charge hose
(for R410A)

Service port

Stop

valve

PURGING PROCEDURES

Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor
and the outdoor units.

Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe.
(The stop valve will not work in its initial state fresh out of the factory (totally closed
with cap on).)

Connect the gage manifold valve and the vacuum pump to the service port of the
stop valve on the gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gage manifold valve, then close the gage manifold valve,
and stop the vacuum pump.

Leave it as is for one or two minutes. Make sure the pointer of the gage manifold
valve remains in the same position. Confirm that the pressure gage show -0.101
MPa (-760 mmHg)

Pipe length :

7 m maximum

No gas charge is needed.

Pipe length exceeding 7 m

Charge the prescribed

amount of gas.

Remove the gage manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on
gas and liquid pipe sides.
Operating without fully opening lowers the performance and causes trouble.

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

Summary of Contents for Mr. Slim SUZ-KA25

Page 1: ...het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condiz...

Page 2: ...ing down the refrigerant stop the compressor before discon necting the refrigerant pipes The compressor may burst if air etc get into it Caution Perform grounding Do not connect the ground wire to a gas pipe water pipe arrester or tele phone ground wire Defective grounding could cause an electric shock Do not install the unit in a place where an inflammable gas leaks If gas leaks and accumulates i...

Page 3: ...air inlet side facing the wall To prevent exposure to wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Units should be installed by licensed contractor accordingly to local code re quirement SUZ KA50 KA60VA2 Air outlet 2 10 mm 21 mm slot Air inlet 285 40 344 5 304 325 800 500 150 400 44 Drainage hole W42 In case of Heater models W33 69 Drain hose Drain so...

Page 4: ...1 4 0 8 mm 8 mm For gas 12 7 1 2 0 8 mm 8 mm SUZ KA60 For liquid 6 35 1 4 0 8 mm 8 mm For gas 15 88 5 8 0 8 mm 8 mm SUZ KA71 For liquid 9 52 3 8 0 8 mm 8 mm For gas 15 88 5 8 1 0 mm 8 mm 2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation 3 Refrigerant pipe bending radius must be 100 mm or more Caution Using careful insulation of specified thickness Excessive thickness...

Page 5: ...r the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R410A 0 101 MPa 760 mmHg Handle Low Handle High Window Charge hose for R410A Vacuum pump Adapter for preventing the back flow Charge hose for R410A Service port Stop valve PURGING PROCEDURES Connect the refrigerant pipes both the liquid and gas pipes betw...

Page 6: ...er than other cables E Power supply cord Caution Use care not to make miswiring Firmly tighten the terminal screws to prevent then from loosening After tightening pull the wires lightly to confirm that they do not move Connect cable from the indoor unit correctly on the terminal block Use the same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra leng...

Page 7: ...1 Min 1 5 1 Min 2 0 1 Min 2 5 Indoor unit Outdoor unit 3 1 5 Polar 3 1 5 Polar 3 1 5 Polar Indoor unit Outdoor unit earth 1 Min 1 5 1 Min 1 5 1 Min 1 5 Circuit rating Outdoor unit L N 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S1 S2 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S2 S3 2 DC 12 V DC 24 V DC 12 V DC 24 V DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separat...

Page 8: ... RG79D664H01 Printed in Thailand Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Reviews: