1. Safety precautions

1.3. Before electric work 

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.
•  For the power lines, use standard cables of suf

¿

 cient capacity. Otherwise, a 

short circuit, overheating, or 

¿

 re may result.

• When installing the power lines, do not apply tension to the cables. If the 

connections are loosened, the cables can snap or break and overheating or 

¿

 re may result.

•  Be sure to ground the unit. Do not connect the ground wire to gas or water 

pipes, lighting rods, or telephone grounding lines. If the unit is not properly 
grounded, electric shock may result.

•  Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and 

molded case circuit breaker) with the speci

¿

 ed capacity. If the circuit breaker 

capacity is larger than the speci

¿

 ed capacity, breakdown or 

¿

 re may result.

1.4. Before starting the test run

 Caution:

• Turn on the main power switch more than 12 hours before starting opera-

tion. Starting operation just after turning on the power switch can severely 
damage the internal parts. Keep the main power switch turned on during the 
operation season.

•  Before starting operation, check that all panels, guards and other protective 

parts are correctly installed. Rotating, hot, or high voltage parts can cause 
injuries.

•  Do not touch any switch with wet hands. Electric shock may result.

• Do not touch the refrigerant pipes with bare hands during operation. The 

refrigerant pipes are hot or cold depending on the condition of the 

À

 owing 

refrigerant. If you touch the pipes, burns or frostbite may result.

• After stopping operation, be sure to wait at least 

¿

 ve minutes before turn-

ing off the main power switch. Otherwise, water leakage or breakdown may 
result.

1.5. Using R410A refrigerant air conditioners

 Caution:

•  Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, 

to connect the refrigerant pipes. Make sure the insides of the pipes are clean 
and do not contain any harmful contaminants such as sulfuric compounds, 
oxidants, debris, or dust. Use pipes with the speci

¿

 ed thickness. (Refer to 

page 5) Note the following if reusing existing pipes that carried R22 refriger-
ant.

- Replace the existing 

À

 are nuts and 

À

 are the 

À

 ared sections again.

- Do not use thin pipes. (Refer to page 5)

•  Store the pipes to be used during installation indoors and keep both ends of 

the pipes sealed until just before brazing. (Leave elbow joints, etc. in their 
packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete-
rioration or compressor breakdown may result.

•  Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the 

À

 ared sections. If mineral oil is mixed in the refrigeration 

oil, oil deterioration may result.

•  Do not use refrigerant other than R410A refrigerant. If another refrigerant is 

used, the chlorine will cause the oil to deteriorate.

•  Use the following tools speci

¿

 cally designed for use with R410A refrigerant. 

The following tools are necessary to use R410A refrigerant. Contact your 
nearest dealer for any questions.

Tools (for R410A)

Gauge manifold

Flare tool

Charge hose

Size adjustment gauge

Gas leak detector

Vacuum pump adapter

Torque wrench

Electronic refrigerant charging scale

•  Be sure to use the correct tools. If dust, debris, or moisture enters the refrig-

erant lines, refrigeration oil deterioration may result.

• Do not use a charging cylinder. If a charging cylinder is used, the composi-

tion of the refrigerant will change and the ef

¿

 ciency will be lowered.

2. Installation location

2.1. Refrigerant pipe (Fig. 2-1) 

   Check that the difference between the heights of the indoor and outdoor 

units, the length of refrigerant pipe, and the number of bends in the pipe are 
within the limits shown below.

Models 

A

Pipe length 

(one way)

B

Height

difference

C

Number of 

bends (one way)

PUZ-A12, A18

Max. 30 m, 100 ft

Max. 30 m,100 ft

Max. 15

PUZ-A24, A30, A36, A42 Max. 50 m, 165 ft

Max. 30 m,100 ft

Max. 15

PUY-A12, A18

Max. 50 m, 165 ft

Max. 30 m,100 ft

Max. 15

PUY-A24, A30, A36, A42 Max. 69 m, 225 ft

Max. 30 m,100 ft

Max. 15

• Height difference limitations are binding regardless of which unit, indoor or out-

door, is positioned higher.

 

D

 Indoor unit

 

E

 Outdoor unit

2.2. Choosing the outdoor unit installation location

•  Avoid locations exposed to direct sunlight or other sources of heat.
•  Select a location from which noise emitted by the unit will not inconvenience neigh-

bors.

•  Select a location permitting easy wiring and pipe access to the power source and 

indoor unit.

•  Avoid locations where combustible gases may leak, be produced, 

À

 ow, or accumu-

late.

•  Note that water may drain from the unit during operation.
•  Select a level location that can bear the weight and vibration of the unit.
• Avoid locations where the unit can be covered by snow. In areas where heavy 

snow fall is anticipated, special precautions such as raising the installation location 
or installing a hood on the air intake must be taken to prevent the snow from block-
ing the air intake or blowing directly against it. This can reduce the air

À

 ow and a 

malfunction may result.

•  Avoid locations exposed to oil, steam, or sulfuric gas.
•  Use the transportation handles of the outdoor unit to transport the unit. If the unit is 

carried from the bottom, hands or 

¿

 ngers may be pinched.

2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)

Fig. 2-1

A

B

E

D

C

Fig. 2-2

31-7/8

11-13/16+29/32

24-13/1

6

6-3/32

19-11/16

2-15/32

13

 

37-13/32

13+1-3/16

37-1/8

6-7/8

23-5/8

14-9/16

   A12, A18

   A36, A42

(inch)

(inch)

(inch)

   A24, A30

Summary of Contents for Mr.SLIM PUZ-A NHA7 Series

Page 1: ...horoughly before installing the air conditioner unit MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de air...

Page 2: ...moisture enter the unit electric shock or re may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may res...

Page 3: ...geration oil applied to the Àared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools speci cally designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Contact your n...

Page 4: ...l the optional air outlet guides for upward airÀow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for A36 A42 models is 1000 mm 39 3 8 inch or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for A36 A42 models is 1000 mm 39 3 8 inch or more 5 Single parallel unit arrangement Fig 2 16 When using an opti...

Page 5: ...to break them Bend radii of 100 mm 3 15 16 inch to 150 mm 5 27 32 inch are suf cient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil Applied on site Warning When installi...

Page 6: ... C D E F G D B A C Fig 4 4 D G B A I F E J H Fig 4 5 1 Fig 4 6 Notes 1 The gure to the left is an example only The stop valve shape service port po sition etc may vary according to the model 2 Turn section A only Do not further tighten sections A and B together C Charge hose D Service port 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 20 m 70 f...

Page 7: ... Fig 6 1 Fig 6 2 1 Remove the service panel 2 Wire the cables referring to the Fig 6 1 and the Fig 6 2 Fig 6 1 Fig 6 2 A12 A18 A C C E E E E E S3 S3 S2 S1 S2 S1 L1 L2 GR A B B D D A A24 A42 L1 GR L2 S1 S2 S3 A B C D E L1 GR L2 S1 S2 S3 A Indoor unit B Outdoor unit C Remote controller D Main switch Breaker E Earth A Earth terminal B Terminal block C Clamp D Service panel E Wire the cables so that t...

Page 8: ...8 A12 A18 A24 A42 TERMINAL BED CABLE STRAP CORD COVER CONDUIT COVER SERVICE PANEL CONDUIT PLATE accessory ...

Page 9: ... power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season 6 2 Field electrical wiring Outdoor unit model A12 A18 A24 A30 A36 A42 Outdoor unit power supply N single 60Hz 208 230 V N single 60Hz 208 230 V N single 60Hz 208 230 V N ...

Page 10: ...e that the low pressure is lowered to near 0 MPa gauge Warning When pumping down the refrigerant stop the compressor before disconnect ing the refrigerant pipes The compressor may burst if air etc get into it A Circuit diagram example Demand function B On site arrangement X Y Relay 8 2 Demand function on site modi cation Fig 8 2 By performing the following modi cation energy consumption can be red...

Page 11: ...ulsory defrosting Start Normal 2 Error history clear Clear Normal 3 4 5 6 Refrigerant system ad dress setting Settings for outdoor unit addresses 0 to 15 TB1 A G F A A E B B B B B D C TB1 TB1 TB4 TB5 TB4 TB5 TB4 TB4 TB5 TB4 1 1 2 ON OFF ON OFF ON OFF 3 4 5 6 3 4 5 6 3 4 5 6 ON OFF 2 10 Low ambient cooling Precautions for low ambient cooling If the outdoor temperature is 23 F or lower during coolin...

Page 12: ...limatiseur peut entraîner des défaillances mécaniques des dysfonctionnements du système ou une panne de l appareil Dans le pire des cas cela peut entraîner un obstacle à la mise en sécurité du produit Le couvercle du bloc de sortie de l appareil extérieur doit être solidement xé S il n est pas correctement installé et si des poussières et de l humidité s in ltrent dans l appareil un choc électriqu...

Page 13: ... comme huile réfrigérante sur les sections évasées Le mélange d huile minérale et d huile réfrigérante peut affecter la qualité de l huile Ne pas utiliser un réfrigérant autre que le réfrigérant R410A Si c est le cas le chlore peut affecter la qualité de l huile Utiliser les outils suivants spécialement conçus pour une utilisation avec le réfrigérant R410A Les outils suivants sont nécessaires pour...

Page 14: ...ir vers le haut 3 Obstacles uniquement à l avant Fig 2 14 Lors de l utilisation d un guidage de sortie d air en option le jeu des modèles A36 A42 est de 1000 mm 39 3 8 inch minimum 4 Obstacles uniquement à l avant et à l arrière Fig 2 15 Lors de l utilisation d un guidage de sortie d air en option le jeu des modèles A36 A42 est de 1000 mm 39 3 8 inch minimum 5 Disposition pour un seul appareil par...

Page 15: ...100 mm 3 15 16 inch à 150 mm 5 27 32 inch suf sent Véri er que les tuyaux ne touchent pas le compresseur Des vibrations ou des bruits anormaux pourraient se produire 1 Raccorder les tuyaux en commençant par l appareil intérieur Serrer les écrous évasés à l aide d une clé dynamométrique 2 Evaser les conduits de liquide et de gaz puis appliquer un lm mince d huile réfrigérante application sur site A...

Page 16: ...aire par la vanne d arrêt de liquide après avoir vidé les extensions de tuyaux et l appareil intérieur Lors de l utilisation de l appareil ajouter du réfrigérant par le clapet de non retour du gaz à l aide d un chargeur de sécurité Ne pas ajouter de réfrigérant liquide directement par le clapet de non retour 2 Une fois l appareil chargé de réfrigérant noter la quantité de réfrigérant ajouté sur l ...

Page 17: ...reil extérieur Fig 6 1 Fig 6 2 1 Retirer le panneau de service 2 Effectuer le câblage conformément aux gures 6 1 et 6 2 A12 A18 A24 A42 L1 GR L2 S1 S2 S3 A Appareil intérieur B Appareil extérieur C Télécommande D Interrupteur fusible principal Disjoncteur E Mise à la terre Pour alimentation Pour alimentation A Borne de terre B Embase de borne C Attache D Panneau de service E Acheminer les câbles d...

Page 18: ...18 A12 A18 A24 A42 TERMINAL BED SANGLE A CABLE PANNEAU DE SERVICE COUVRE CABLE COUVRE TUBE PLAQUETTE DE TUBE accessoire ...

Page 19: ...nt mettre l alimentation principale hors tension lors de l entretien Veiller également à ne pas toucher les bornes S1 S2 et S3 lorsque l alimentation est sous tension S il faut placer un sectionneur entre les appareils extérieur et intérieur en utiliser un de type tripolaire 7 Marche d essai 7 1 Avant la marche d essai Lorsque l installation le tuyautage et le câblage des appareils intérieur et ex...

Page 20: ...mode d essai ne peut pas être modifié via le commutateur DIP SW4 2 lors de la marche d essai Pour ce faire arrêter l essai via le commutateur DIP SW4 1 Une fois le mode modi é reprendre l essai via le commutateur SW4 1 7 2 2 Utilisation de la télécommande Reportez vous au manuel d installation de l appareil intérieur 7 Marche d essai Les points suivants doivent être contrôlés également L appareil ...

Page 21: ... Normal 3 4 5 6 Réglage des adresses du système de réfrigérant Réglages des adresses des appareils extérieurs de 0 à 15 TB1 A G F A A E B B B B B D C TB1 TB1 TB4 TB5 TB4 TB5 TB4 TB4 TB5 TB4 1 1 2 ON OFF ON OFF ON OFF 3 4 5 6 3 4 5 6 3 4 5 6 ON OFF 2 10 Rafraîchissement à basse température ambiante Précautions pour le rafraîchissement à basse température ambiante Si la température extérieure est in...

Page 22: ... la uni dad En el peor de los casos podría suponer un grave impedimento para garantizar la seguridad del producto La cubierta del bloque de terminales de la unidad exterior tiene que estar bien sujeta Si la cubierta no se instala correctamente y el polvo y la hume dad entran en la unidad se pueden producir una descarga eléctrica o un incendio Utilice sólo accesorios autorizados por Mitsubishi Elec...

Page 23: ... aceite de éster de éter o alquilobenceno en pequeñas cantidades para recubrir las secciones abocardadas Si se mezcla aceite mineral con aceite de refrigeración se puede deteriorar el aceite No utilice otro refrigerante que no sea R410A Si utiliza otro refrigerante el cloro provocará el deterioro del aceite Utilice las siguientes herramientas especialmente diseñadas para usar con el refrigerante R...

Page 24: ...stáculos sólo en la parte trasera y superior Fig 2 13 No se deben instalar más de tres unidades correlativas Además se debe dejar el espacio indicado No utilice las guías para salida de aire opcionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 14 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos A36 A42 debe ser de 1000 mm 39...

Page 25: ...ncluso la extracción de una tubería Cuando doble los tubos tenga cuidado de no romperlos Un radio de curvatura de 100 mm 3 15 16 inch a 150 mm 5 27 32 inch es su ciente Asegúrese de que las tuberías no tocan el compresor Podría producir ruidos o vibraciones extrañas 1 Las tuberías se deben conectar empezando por la unidad interior Las tuercas abocardadas se deben apretar con una llave dinamométric...

Page 26: ...guela con el refrigerante adicional a través de la válvula de parada de líquido después de haber aspirado los tubos y la unidad interior Si la unidad está en marcha añada refrigerante a la válvula de reten ción de gas con un cargador seguro No añada refrigerante líquido directa mente a la válvula de retención 2 Después de haber cargado la unidad con refrigerante apunte la cantidad de refrigerante ...

Page 27: ...traiga el panel de servicio 2 Tienda los cables de acuerdo con la Fig 6 1 y Fig 6 2 A12 A18 A24 A42 L1 GR L2 S1 S2 S3 A Unidad interior B Unidad exterior C Controlador remoto D Interruptor fusible principal Diferencial E Conexión a tierra Fig 6 1 Fig 6 2 A C C E E E E E S3 S3 S2 S1 S2 S1 L1 L2 GR A B B D D A A B C D E L1 GR L2 S1 S2 S3 A Tierra del terminal B Bloque de terminales C Grapa D Panel d...

Page 28: ...28 A12 A18 A24 A42 PLACA DEL CONDUCTO accesorio BANCO DE TERMINALES BRIDA DE DE SUJECIÓN CABLES CUBIETRA DE CABLES CUBIERTA DEL CONDUCTO PANEL DE SERVICIO ...

Page 29: ...dado El compresor no funcionará a menos que la conexión de fase de la fuente de alimentación sea correcta Conecte la corriente al menos 12 horas antes de que empiece a funcionar el equipo Si se acciona inmediatamente después de haberlo conectado a la corriente pue den producirse daños graves en las piezas internas Mantenga la unidad conec tada a la corriente durante la temporada de funcionamiento ...

Page 30: ...cia de presión de las tuberías La unidad no está averiada El modo de prueba de funcionamiento no se puede cambiar por el conmuta dor DIP SW4 2 durante la prueba Para cambiar el modo de prueba de func ionamiento durante la prueba pare la prueba con el conmutador DIP SW4 1 Después de cambiar el modo de prueba de funcionamiento reanude la prueba con el conmutador SW4 1 7 2 2 Uso del control remoto Co...

Page 31: ...o Iniciar Normal 2 Borrado del registro histórico de errores Borrar Normal 3 4 5 6 Ajuste de la dirección del sistema refrigerante Ajustes de las direcciones 0 a 15 de la unidad exterior TB1 A G F A A E B B B B B D C TB1 TB1 TB4 TB5 TB4 TB5 TB4 TB4 TB5 TB4 1 1 2 ON OFF ON OFF ON OFF 3 4 5 6 3 4 5 6 3 4 5 6 ON OFF 2 10 Refrigeración con temperatura baja Precauciones para la refrigeración con temper...

Page 32: ...6 24 40 80 40 60 20 32 6 40 60 12 20 16 24 79 119 Fig 2 6 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 12 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 4 8 4 8 8 12 20 40 4 6 Fig 2 7 Max 20 8 12 40 Fig 2 11 6 10 6 10 40 60 12 20 Max 20 Fig 2 13 12 26 40 60 Max 12 40 60 ...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ... 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment BG79U896H11 Printed in Japan ...

Reviews: