4

Check the pitch of the suspension bolt. (340 mm 

×

 811 mm) (Fig. 2-7)

1. Thread washers 

1

 

2

 (supplied) and their nuts (procured locally) onto the sus-

pension bolt in advance.
* Do this in the following order (from the top): nut, insulated washer 

2

, washer

without insulation 

1

, two nuts.

* Position insulated washer 

2

 with the insulated surface pointing down, as in the

figure.

2. Lift the unit into place, aligned properly with the suspension bolt. Pass the bracket

between washers 

1

 and 

2

, which are already in place, and secure it. Do the

same in all four places.
* Make sure the suspension bolt extends 20 mm or more from the surface of the

ceiling. Otherwise you will not be able to install the cover panel (sold separately).

3. If the long opening in the bracket and opening in the ceiling do not align, adjust

them until they do.

4. Check that the four corners are all level, using a spirit level or clear plastic tubing

with water in it.
* Make sure that any slant in the unit after installation is less than 0.5 degrees

(approx. 6 mm on the long dimension of the unit).

5. Tighten all the nuts. (Fig. 2-8)

F

G

B

B

C

*

E

*

D

C

A

11

2

Min. 20

B

11

0

11

0

A

C

D E

(mm)

(mm)

Fig. 2-7

A

Suspension bolt (3/8" or M10)

B

Ceiling surface

C

Nut (3/8" or M10)

D

Washer 

2

 (with insulation)

E

Washer 

1

F

(Install with insulation facing down)

G

Measurement to upper face of bracket

A

Suspension bolt (3/8" or M10)

B

Clear plastic tubing

C

Underside of bracket

D

Secure front panel here

E

Make these surfaces are flush with each other (0 - 3 mm)

Fig. 2-8

D

E

F G

340

811

K

L

M

J

H

I

A
C
D

E
C

 *1

B

Min. 20

Min. 30

(mm)

(mm)

Fig. 2-5

Fig. 2-6

D

Ceiling panel

E

Rafter

F

Beam

G

Roof beam

H

Use inserts rated at 100-150 kg each (procure locally)

I

Suspension bolts M10 (3/8") (procure locally)

J

Steel reinforcing rod

K

C channel

L

Channel suspension bracket

M

M10 suspension bolt

2.4. Unit suspension procedures (Fig. 2-6)

Procure 3/8" bolts or M10 bolts locally.
• Adjust the length of the bolt’s protrusion from the ceiling surface beforehand.

*1. When using an extra upper nut in suspending the unit, in some cases you may

have to add it later.

A

Suspension bolt

B

Ceiling panel

C

Nut

D

Washer (with insulation) 

2

E

Washer (without insulation) 

1

2. Installing the indoor unit

1

Wooden structures (Fig. 2-5)

• Use tie beams (single storied houses) or second floor beams (two story houses) as

reinforcing members.

• Wooden beams for suspending air conditioners must be sturdy and their sides

must be at least 6 cm long if the beams are separated by not more than 90 cm and
their sides must be at least 9 cm long if the beams are separated by as much as
180 cm. The size of the suspension bolts should be ø10 (3/8"). (The bolts do not
come with the unit.)

• Use channel, duct and other parts procured locally to suspend the indoor unit.

2

Ferro-concrete structures

Secure the suspension bolts using the method shown, or use steel or wooden hang-
ers, etc. to install the suspension bolts.

Summary of Contents for Mr.SLIM PMH-P BA Series

Page 1: ...re il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ ÚÈÓ...

Page 2: ...tall the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical ca...

Page 3: ...ay be gaps between it and the indoor unit This may result in dripping water or other problems When deciding on placement consider carefully the space around the ceiling and make your measurements generous Ceiling types and building construction differ Therefore you should consult with the builder and decorator Using the installation template top of the package and the gauge supplied as an accessor...

Page 4: ...t 3 8 or M10 B Clear plastic tubing C Underside of bracket D Secure front panel here E Make these surfaces are flush with each other 0 3 mm Fig 2 8 D E F G 340 811 K L M J H I A C D E C 1 B Min 20 Min 30 mm mm Fig 2 5 Fig 2 6 D Ceiling panel E Rafter F Beam G Roof beam H Use inserts rated at 100 150 kg each procure locally I Suspension bolts M10 3 8 procure locally J Steel reinforcing rod K C chan...

Page 5: ...e a charging cylinder Be especially careful when managing the tools Do not use commercially available dryers 3 2 Indoor unit Fig 3 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu la...

Page 6: ...unit in Cooling mode 3 Check for water drainage at the transparent check window and the outlet of the drainage pipe 4 Stop the test run Don t forget to turn off the power Fig 4 3 Fig 4 1 Fig 4 2 A Ceiling panel B Max 60 cm C Position of drain outlet D Make as short as possible Max 15 cm E Make as small as possible F Downward slope 1 100 or more G Make as great as possible Min 10 cm H Drainage pipe...

Page 7: ...245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Heater Indoor unit input capacity Heater 1 Main switch Breaker Indoor unit power supply Heater Indoor unit power supply Heater earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit earth 2 Remote controller Indoor unit 3 Indoor unit Heater L N 4 Indoor unit Outdoor unit S1 S2 4 Indoor unit Outdoor...

Page 8: ...nt address Unit number 1 2 3 4 Function table Select unit number 00 Mode Power failure automatic recovery Indoor temperature detecting LOSSNAY connectivity Power voltage Settings Not available Available 1 Indoor unit operating average Set by indoor unit s remote controller Remote controller s internal sensor Not Supported Supported indoor unit is not equipped with outdoor air intake Supported indo...

Page 9: ...the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures refer to the operation manual for the indoor unit Fig 6 2 Output pattern A Er...

Page 10: ...on device is not con nected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of function selection Correct operation For description of each LED LED 1 2 3 provided on the indoor controll...

Page 11: ... press the intake grille on the place marked Push until you hear it snap into place 7 4 Checks after installing Check that there are no gaps between the indoor unit and the front panel and between the front panel and the ceiling surface If there are gaps the wind may come in and condensation may result Check that the air filter is in place 7 3 Installing the grille Open the intake grille by pressi...

Page 12: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U613H01 The product at hand is based on the following EU regulations ...

Reviews: