2. Installation location

Refer to the outdoor unit installation manual.

3. Installing the indoor unit

3.1. Check the indoor unit accessories (Fig. 3-1)

The indoor unit should be supplied with the following accessories.

Accessory name

Q’ty

1

Installation template

1

2

Washers (with insulation)

4

Washers (without insulation)

4

3

Pipe cover (for refrigerant piping joint)
small diameter

1

large diameter

1

4

Band (large)

6

Band (small)

2

5

Screw with washer (M5 

×

 25) for mounting grille

4

6

Drain socket

1

7

Insulation

1

3

2

5

4

7

6

Fig. 3-1

1

3.2. Ceiling openings and suspension bolt installation

locations (Fig. 3-2)

• Using the installation template (top of the package) and the gauge (supplied as an

accessory with the grille), make an opening in the ceiling so that the main unit can
be installed as shown in the diagram. (The method for using the template and the
gauge are shown.)

* Before using, check the dimensions of template and gauge, because they

change due to fluctuations of temperature and humidity.

* The dimensions of ceiling opening can be regulated within the range shown in

following diagram; so center the main unit against the opening of ceiling, en-
suring that the respective opposite sides on all sides of the clearance between
them becomes identical.

• Use M10 (3/8") suspension bolts.

* Suspension bolts are to be procured at the field.

• Install securely, ensuring that there is no clearance between the ceiling panel &

grille, and between the main unit & grille.

A

Outer side of main unit

B

Bolt pitch

C

Ceiling opening

D

Outer side of Grille

E

Grille

F

Ceiling

G

Multi function casement (option)

H

Entire periphery

*

Note that the space between ceiling panel of the unit and ceiling slab and etc must be 10 to
15 mm.

159

192

159

159

98

860–910

20–45

20

45

20

45

20–45

810

950

840

197

159

605

840

950

860

910

A

B

C

D

C

B

D

A

135

F

G

E

17

+5

  0

17

+5

  0

50

70

105

30

C

D

Min. 1000

Min. 500

F

H

E

Fig. 3-2

Models

C

D

RP3

241

258

RP4,5,6

281

298

(mm)

Summary of Contents for Mr Slim PLA-RP-AA

Page 1: ...Air Conditioners PLA RP AA English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Page 2: ... around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dr...

Page 3: ...wn Before using check the dimensions of template and gauge because they change due to fluctuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in following diagram so center the main unit against the opening of ceiling en suring that the respective opposite sides on all sides of the clearance between them becomes identical Use M10 3 8 suspe...

Page 4: ...g plate Make sure that step A is performed within 17 22 mm Damage could result by failing to adhere to this range Fig 3 6 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior to installation of the decorative cover or when ap plying ceiling materials 3 6 Confirming the position of main unit and tighten ing the suspension bolts Fig 3...

Page 5: ...36 100 120 Indoor unit Liquid Indoor unit Gas Outdoor unit Liquid Outdoor unit Gas RP3 Flare nut attached to indoor liquid valve Flare nut attached to indoor gas valve Flare nut attached to outdoor liquid valve Flare nut attached to outdoor gas valve RP4 6 Flare nut attached to indoor liquid valve Flare nut in outdoor unit accessories Flare nut attached to outdoor liquid valve Flare nut attached t...

Page 6: ...with a band Both insulating material and band are supplied with the unit A Unit B Insulating material C Band large D Drain port transparent E Insertion margin F Matching G Drain pipe O D ø32 PVC TUBE H Insulating material purchased locally I Transparent PVC pipe J O D ø32 PVC TUBE Slope 1 100 or more K Band small L Drain socket Max 20m 1 5 2m A B C B M L K D E D H I G D F F F Max 15cm J F G 11 25 ...

Page 7: ...ntroller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exposed to cold or hot winds Area in which the remote controller can be operated easily Area in which the remote controller is beyond the reach of children 2 Installation method Fig 7 5 1 Attach the remote controller holder to the desired location using two tapping ...

Page 8: ...e setting depending on the voltage used 1 Go to the function select mode Press the CHECK button F twice continuously Start this operation from the status of remote controller display turned off CHECK is lighted and 00 blinks Press the temp button C once to set 50 Direct the wireless remote controller toward the receiver of the indoor unit and press the h button A 2 Setting the unit number Press th...

Page 9: ... circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0MΩ Insulation resistance 8 2 Test run The following 3 methods are available 8 2 1 Using wired remote controller Fig 8 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is...

Page 10: ...rheating safeguard operation Single beep 6 Lit for 1 sec 6 P8 Pipe temperature error Single beep 8 Lit for 1 sec 8 P9 TH5 sensor error Single beep 2 Lit for 1 sec 2 U0 UP Outdoor unit error Double beep 1 Lit for 0 4 sec 0 4 sec 1 F1 FA Outdoor unit error Double beep 1 Lit for 0 4 sec 0 4 sec 1 E0 E5 Signal error between remote controller and indoor units Sounds other than above Lights other than a...

Page 11: ... to 5 cm B Cover of water supply inlet C About 1000 cc D Water E Drain plug 9 System controll Refer to the outdoor unit installation manual 10 1 Checking the contents Fig 10 1 This kit contains this manual and the following parts Accessory name Q ty Remark 1 Grille 1 950 950 mm 2 Screw with captive washer 4 M5 0 8 25 3 Gauge 1 Divided into four parts 4 Fastener 2 5 Screw 4 4 8 6 Wireless remote co...

Page 12: ...at there are no gaps E Adjust the nut of the main unit using a wrench etc Fig 10 7 A D C B E Fig 10 8 A Clamp of the main unit B Tube C Connector of the main unit D Grille connector E Fastener 10 4 4 Wire connection Fig 10 8 Be sure to connect the unit to the connector white 10 pole Next attach the white glass tube that comes with the main unit so that the tube covers the connector Close the openi...

Page 13: ...n the unit and the grille or between the grille and the surface of the ceiling If there is any gap between the unit and the grille or between the grille and the surface of the ceiling it may cause dew to collect Make sure that the wires have been securely connected C A B A Screw 4 8 5 B Corner panel C Safety wire D H G E F Fig 10 11 10 8 Installing the intake grille Fig 10 11 Note When reinstallin...

Page 14: ... sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U017H02 ...

Reviews: