10
6. Electrical work
7. Test run
Function table
Select unit number 00
Mode
Settings
Mode No.
Setting no.
Initial setting
setting
Wired remote controller
(RF thermostat)
Power failure automatic recovery
Not available
01
(101)
1
Available *1
2
Indoor temperature detecting
Indoor unit operating average
02
(–)
1
Set by indoor unit’s remote controller
2
Wired remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
(103)
1
Supported (indoor unit is not equipped with outdoor-air intake)
2
Supported (indoor unit is equipped with outdoor-air intake)
3
Power voltage
230 V
04
(104)
1
208 V
2
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Settings
Mode No.
Setting no.
Initial setting
setting
Wired remote controller
(RF thermostat)
Filter sign
100Hr
07
(107)
1
2500Hr
2
No fi lter sign indicator
3
Fan speed
Silent
08
(108)
1
Standard
2
High ceiling
3
No. of air outlets
4 directions
09
(109)
1
3 directions
2
2 directions
3
Installed options (high-perform-
ance fi lter)
Not supported
10
(110)
1
Supported
2
Up/down vane setting
Equipped with vanes (vanes angle setup
3
)
11
(111)
1
Equipped with vanes (vanes angle setup
1
)
2
Equipped with vanes (vanes angle setup
2
)
3
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
7.1. Before test run
After completing installation and the wiring and piping of the indoor and out-
door units, check for refrigerant leakage, looseness in the power supply or
control wiring, wrong polarity, and no disco
nnection
of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 M .
Do not carry out this test on the control wiring (low voltage circuit)
terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 M .
7.2. Test run
Refer to the installation manual that comes with each remote controller for de-
tails.
7.3. Self-check
Refer to the installation manual that comes with each remote controller for de-
tails.
RF thermostat is not established.