43
2-10 INDOOR FAN CONTROL
Indoor fan relay output.
(a) During fan ON
The indoor fan relay turns ON. One second later, the phase control will start.
(b) During fan OFF
The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
3. SW3 (Emergency operation switch)
1 2
Normal operation
ON
OFF
1 2
For emergency cooling
ON
OFF
1 2
For emergency heating
ON
OFF
4. SW5 (Model selector)
1 2 3 4
ON
OFF
SW5-1) Not for use.
SW5-2) Leave this switch as it is.
SW5-3) Not for use.
SW5-4) Not for use.
5. SW6 (Address selector)
1 2 3 4
ON
OFF
6. SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time.
The initial factory setting by is based on each capacity.
Service Ref.
SW7
PKH30FK3
PKH36FK3
1 2 3
ON
OFF
1 2 3
ON
OFF
PKH24FK3
1 2 3
ON
OFF
PKH18FK3
1 2 3
ON
OFF
7. SW8 (Option)
SW8-1~2) Not for use.
SW8-3~4) Not for use.
SW8-5) Not for use.
SW8-6) OFF:For 230V power supply
ON: For 208V power supply
1 2 3 4
ON
OFF
5 6
8. SW9 (Model selector)
SW9-1~5) Keep this switch.
1 2 3 4
ON
OFF
5
This switch is not available for series PKH.
2. SW2 (Address selector)
1 2 3 4 5 6
ON
OFF
Used in setting the unit-address for group control.
For further information,refer to page OC273-51.