25
w
8—9 Refer to page OC273-24.
w
12
When room temperature is 64°F or below, the compressor cannot operate.
When room temperature rises over 64°F the compressor starts after a 3-minute time delay.
w
13
Compressor ON time is decided by room temperature. Refer to page OC273-32.
w
14
In dry operation, compressor ON makes the fan speed LOW. Also, when the compressor OFF and the pipe temperature
is 79°F or less, the fan stops, or when the compressor OFF and the pipe temperature is below 43°F the fan speed
changes to LOW mode.
It is not possible to set the fan speed with the remote controller.
DRY OPERATION
DRY
operation
Four-way valve / OFF
Initial dry
operation
Room temperature is
64
°
F or lower
During
compressor ON
Compressor &
thermostat ON
Vane initial setting
Vane
setting notch
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
3-minute
time delay
10-minute
compressor
OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Compressor &
thermostat
ON
3-minute
compressor
operation
Compressor ON
time completes
NO
YES
NO
NO
YES
w
14
w
14
w
13
YES
YES
NO
YES
NO
NO
w
9
YES
YES
w
9
NO
NO
w
12
YES
NO
YES
w
8
OC273-A-1.qxp 03.11.25 8:59 AM Page 25