27
OCH758
9-7. TEST POINT DIAGRAM
Indoor controller board
CN2L
Connector
(LOSSNAY)
LED1: Power
supply (I.B)
CN105
IT Terminal
CN4F
Float switch (FS)
(option)
CN41
Connector
(HA terminal-A)
SWE
Emergency
operation connector
CN51
Centrally control
CNP Drain pump output
1
–
3
: 13 VDC
(option)
CNMF
Connect to the
fan motor (MF)
1
–
3
: 310–340 VDC
4
–
3
: 15 V DC
5
–
3
: 0–6.5 VDC
6
–
3
: 0 or 15 VDC
CN01
Connect to the
Terminal block (TB4)
1
–
3
: 220–240 V AC
FUSE
(3.15 A 250 V)
CN3C
Transmission
(Indoor/outdoor)
(0–28 VDC)
CN44
Pipe temperature
thermistor
1
–
2
: Liquid (TH2)
3
–
4
: Condenser/
Evaporator(TH5)
CN90
Connect to the remote
operation adapter
CN22
Connect to the terminal
block (TB5) (Remote
controller connecting
wire) (option)
CNRU
Connect to SWITCH BOARD
(S.B), LED BOARD (L.B) and
PCB for WIRELESS REMOTE
CONTROLLER (option)
CN20
Room temp.
thermistor (TH1)
CNV
Vane motor
(MV1, MV2)
12 VDC pulse outlet
LED2: Power
supply (Wired
remote controller)
Jumper wire J41,J42
Pair No. setting for
wireless remote controller
SW2
Capacity setting
SW1
Model selection
CN32
Remote switch
LED3: Transmission
(Indoor/Outdoor)