1.  Safety precautions .......................................................................................... 2

2.  Indoor unit installation location ....................................................................... 3

3.  Installing the indoor unit ................................................................................. 3

4.  Installing the refrigerant piping ....................................................................... 4

5.  Drainage piping work ....................................................................................... 5

6.  Electrical work ................................................................................................. 6

7.  Duct work (Fig. 7-1) ....................................................................................... 10

8.  Test run .......................................................................................................... 11

1.  Safety precautions

 

Before installing the unit, make sure you read all the “Safety precautions”.

 

Please report to your supply authority or obtain their consent before 
connecting this equipment to the power supply system. 

 Warning:

Describes precautions that must be observed to prevent danger of injury or 

death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions,” use, 

and  maintenance  of  the  unit  to  the  customer  according  to  the  information  in  the 

Operation Manual and perform the test run to ensure normal operation. Both the 

Installation Manual and Operation Manual must be given to the user for keeping. 

These manuals must be passed on to subsequent users.

 : Indicates a part which must be grounded.

Warning:

Carefully read the labels affixed to the main unit.

Warning:

•  Ask a dealer or an authorized technician to install the unit.

•  For installation work, follow the instructions in the Installation Manual and 

use tools and pipe components specifically made for use with refrigerant 

specified in the outdoor unit installation manual.

•  The unit must be installed according to the instructions in order to mini-

mize the risk of damage from earthquakes, typhoons, or strong winds. An 

incorrectly installed unit may fall down and cause damage or injuries.

•  The  unit  must  be  securely  installed  on  a  structure that  can sustain its 

weight. 

•  If the air conditioner is installed in a small room, measures must be taken 

to  prevent  the  refrigerant  concentration  in  the  room  from  exceeding  the 

safety limit in the event of refrigerant leakage. Should the refrigerant leak 

and cause the concentration limit to be exceeded, hazards due to lack of 

oxygen in the room may result.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•  All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. 

•  Use only specified cables for wiring.

•  The terminal block cover panel of the unit must be firmly attached.

•  Use only accessories authorized by Mitsubishi Electric and ask a dealer or 

an authorized technician to install them.

•  The  user should  never  attempt  to  repair  the  unit  or  transfer  it  to  another 

location.

•  After installation has been completed, check for refrigerant leaks. If refrig-

erant leaks into the room and comes into contact with the flame of a heater 

or portable cooking range, poisonous gases will be released.

1.1.  Before installation (Environment)

 Caution:

•  Do  not  use  the  unit  in  an unusual  environment.  If  the  air  conditioner  is 

installed in areas exposed to steam, volatile oil (including machine oil), or 

sulphuric gas, areas exposed to high salt content such as the seaside, the 

performance can be  significantly reduced and the internal parts can be 

damaged.

•  Do not  install  the  unit  where  combustible  gases may leak, be  produced, 

flow, or accumulate. If combustible gas accumulates around the unit, fire or 

explosion may result.

•  Do not keep food, plants, caged pets, artwork, or precision instruments in 

the direct airflow of the indoor unit or too close to the unit, as these items 

can be damaged by temperature changes or dripping water.

•  When  the  room  humidity  exceeds  80%  or  when  the  drainpipe  is  clogged, 

water may drip from the indoor unit. Do not install the indoor unit where 

such dripping can cause damage.

•  When installing the  unit in a  hospital or  communications office, be  pre-

pared for noise and electronic interference. Inverters, home appliances, 

high-frequency medical equipment, and radio communications equipment 

can  cause  the  air  conditioner  to  malfunction  or  breakdown.  The  air  con-

ditioner  may  also  affect  medical  equipment,  disturbing  medical  care,  and 

communications equipment, harming the screen display quality.

1..  Before installation or relocation

 Caution:

•  Be  extremely  careful  when  transporting the  units.  Two  or  more  persons 

are needed to handle the unit, as it weighs 20 kg or more. Do not grasp the 

packaging bands. Wear protective gloves as you can injure your hands on 

the fins or other parts.

•  Be sure to safely dispose of the packaging materials. Packaging materials, 

such as nails and other metal or wooden parts may cause stabs or other 

injuries.

•  Thermal insulation of the refrigerant pipe is necessary to prevent condensation. 

If the refrigerant pipe is not properly insulated, condensation will be formed.

•  Place thermal insulation on the pipes to prevent condensation. If the drain-

pipe is installed incorrectly, water leakage and damage to the ceiling, floor, 

furniture, or other possessions may result.

•  Do not clean the air conditioner unit with water. Electric shock may result.

•  Tighten  all  flare  nuts  to  specification  using  a  torque  wrench.  If  tightened 

too much, the flare nut can break after an extended period.

1.3.  Before electric work

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.

•  For the power lines, use standard cables of sufficient capacity. Otherwise, 

a short circuit, overheating, or fire may result.

•  When installing the power lines, do not apply tension to the cables.

•  Be  sure  to ground  the  unit.  If  the  unit  is  not  properly  grounded,  electric 

shock may result.

•  Use  circuit  breakers (ground fault  interrupter, isolating switch (+B fuse), 

and moulded case circuit breaker) with the specified capacity. If the circuit 

breaker  capacity  is  larger  than  the  specified  capacity,  breakdown  or  fire 

may result.

1.4.  Before starting the test run

 Caution:

•  Turn on the main power switch more than 1 hours before starting opera-

tion. Starting operation just after turning on the power switch can severely 

damage the internal parts.

•  Before starting operation, check that all panels, guards and other protec-

tive  parts  are  correctly  installed.  Rotating,  hot,  or  high  voltage  parts  can 

cause injuries.

•  Do not operate the air conditioner without the air filter set in place. If the air 

filter is not installed, dust may accumulate and breakdown may result.

•  Do not touch any switch with wet hands. Electric shock may result.

•  Do not touch the refrigerant pipes with bare hands during operation.

•  After stopping operation, be sure to wait at least five minutes before turn

-

ing off the main power switch. Otherwise, water leakage or breakdown may 

result.

BG79U935H02.indd   2

2006/12/20   9:31:54

Summary of Contents for Mr.SLIM PE-3EAK

Page 1: ...ION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Air Conditioners PEH 2 5 3 4 5 6EAK PEH 2 5 3 4 5EAKH PE 3 4 5 6EAK PE 3 4EAKT ...

Page 2: ...stible gases may leak be produced flow or accumulate If combustible gas accumulates around the unit fire or explosion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged...

Page 3: ...cted at a fire alarm sensor Hot air could trigger the alarm during the heating operation Avoid places where acidic solutions are frequently handled Avoid places where sulphur based or other sprays are frequently used Warning The unit must be securely installed on a structure that can sustain its weight 2 2 Service space Fig 2 2 Models A B PE H 2 5 3 650 690 PE H 4 920 960 PE 5 6 PEH 5 1120 1160 PE...

Page 4: ...a the service port for the outdoor unit s stop valve 3 After completing procedure 1 or 2 above open the outdoor unit stop valves fully This completes the procedure for connecting the refrigerant circuit between the indoor and outdoor units Instructions for the stop valve are marked on the out door unit Apply a thin layer or refrigerant oil to the pipe and the joint seating surface before tightenin...

Page 5: ... mm Tightening torque kg cm ø9 52 350 420 ø15 88 750 800 ø19 05 1000 1400 If a torque wrench is not available the following method may be used While tightening the flare nut with a spanner stop turning the nut at the point where the tightening torque suddenly increases Then turn the spanner in the angle specified in the table below Approximate additional tightening angle Pipe diameter Tightening a...

Page 6: ...rds 6 2 Electrical The following connection patterns are available The outdoor unit power supply patterns vary on models For cooling only models Simultaneous twin system For heat pump models For cooling only models A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Wired remote controller G I...

Page 7: ...ote controllers setting If two remote controllers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the op eration manual for the indoor unit B 1 B 2 Fig 6 5 30 30 30 120 83 5 46 Fig 6 4 Fig 6 6 Indoor unit model PE PEH Indoor unit power supply Heater N single 50 Hz 220 240 V 60 Hz 220 V N single 50 Hz 220 240 V Indoor uni...

Page 8: ...interface unit 8 Function setting Selecting the unit function and test run cannot be performed from the MA remote controller when connecting it to the Interface MAC 397IF E One remote controller can be used to operate multiple unit Fig 6 9 This function of group control allows to operate multiple units a maxi mum of up to 16 outdoor units as one group with one remote controller Connect interface M...

Page 9: ...igerant address 0 Refrigerant address 1 Refrigerant address 2 Refrigerant address 3 Refrigerant address 4 Refrigerant address 5 Refrigerant address 6 Refrigerant address 7 Refrigerant address 8 Refrigerant address 9 Refrigerant address 10 Refrigerant address 11 Refrigerant address 12 Refrigerant address 13 Refrigerant address 14 Refrigerant address 15 These setting when connecting an MA remote con...

Page 10: ...tem System diagram Remarks 1 Connecting MA remote con troller directly to indoor unit The contents that appear on the displays may differ between the MA remote control ler that is connected to the indoor unit and the MA remote controller that is connected to the interface unit Examples Fan speed Filter sign 2 Using wireless remote con troller on indoor unit 1 Outdoor unit 2 Indoor unit 3 Interface...

Page 11: ...E3 Wired remote controller transmission error E4 E5 Wired remote controller signal receiving error E1 E2 Wired remote control board error If the unit cannot be operated properly after the above test run has been performed refer to the following table to remove the cause Symptom Cause Wired remote controller PLEASE WAIT For about 2 minutes after power on For about 2 minutes after power on operation...

Page 12: ...À Õ â ë Õ à Á Õ À µâπ â ß µ å ß π ª À Õ ËÕß Õ ËµâÕß àπ â π ß Ë Õ å ÕÕ µ ËÕß πÕ À Õµ Èß â âµ ËÕß π ª æ µ ÿ ß à Õ À ª Ë π ª ßÕÿ À Ÿ À Õ À πÈ â ë À Èπ πÀâÕß Ÿß π 80 À Õ àÕ πÈ ÈßÕÿ µ π πÈ Õ À ß µ ËÕß π Õ Õ à µ µ Èßµ ËÕß πÕ π Ë ËßÕ À À πÈ â ë À µ µ Èßµ ËÕß π ßæ À Õ π ß π µ Ë ªí À ß π πÕ Á Õπ å µ ª ß ËÕß â π â π Õÿª å ß æ å Ë Ë Ÿß Õÿª å Ë â ÿ Õ ªìπ Àµÿ Àâ ËÕߪ Õ ß πº ª µ À Õ ÿ â ËÕߪ Õ Õ àߺ µàÕÕÿª å ß ...

Page 13: ...ª åµà ßÊ àÕ Èß µ Õπ µ ËÕß Àâ πàπÀπ ß â ß Ë πÈ Àπ µ ËÕß â 2 2 æ Èπ Ë âß π Fig 2 2 ÿàπ A B PE H 2 5 3 650 690 PE H 4 920 960 PE 5 6 PEH 5 1120 1160 PEH 6 1306 1346 A àÕß Ÿ â B àÕߪ àÕ Õ ÕÕ C π πÈ D µ À π E àÕß Èπ à π ø F æ Èπ Ë âß π 2 µ Àπàß π µ µ Èßµ ËÕß πÕ ÿàπ W D H PE H 2 5 3 785 690 428 PE H 4 1055 690 428 PE 5 6 PEH 5 1255 690 428 PEH 6 1415 690 428 Fig 2 1 Fig 2 2 A B 1 2 3 Fig 3 1 3 1 µ Õ Õÿª...

Page 14: ...ßµ ËÕß πÕ πÕ π π âß π Õß å ªî Õ Ÿà ˵ ËÕß πÕ Õ ë πÈ π Áπ ßÊ Ë àÕ æ Èπº πµ ËÕ àÕπ Ë π ø åπ ë ⪠Õßµ π ËÕ µàÕ àÕ Àâ πàπ ë â π πÀÿâ àÕ Áπ Ë Àâ æ π ÿ µàÕ µ ËÕß πÕ Õ à ß ß µ π π Ë π Àâ A â πÀ ß F µ µàÕ àÕ πÈ Èß µ ºŸâ 1 BSP B àÕ Áπ G àÕßµàÕ ø â C â π â H ä D ºàπ ÕßÕ I Õß À E àÕß Èπ à π ø π àÕ Áπ àÕ πÈ ÿàπ PE 3 PEH 2 5 3 PE 4 5 6 PEH 4 5 6 Õß À ODø9 52 3 8 ODø9 52 3 8 ä ODø15 88 5 8 ODø19 05 3 4 àÕ πÈ OD...

Page 15: ...ËÕß πÕ µ ËÕßÀ b 1 Ω Õ àÕ c 2 d âÕµàÕÀ π e ÿ ËÕ µàÕ f Ω Õ àÕ À ÈÕ âµ âÕßµ g â ª æ ËÕ ÿ ËÕ Àâ πàπ π h Ω Õ àÕ À⪠µ πàπ µ ËÕßÀ Àâ πàπ à Àâ àÕß à ß i µ ËÕß πÕ j ÿ µàÕÀ π k àÕßÕ â l àÕ Áπ m µ ËÕß πÕ Õ n ä o Õß À 1 ß Ë Àπ ⪠Fig 4 3 Õ Ë ß âπºà Ÿπ å ß â ππÕ Õß àÕ Õß ß ß ø9 52 350 420 ø15 88 750 800 ø19 05 1000 1400 ë À à ⪠â Õ â µàÕ ªπ È π Ë π ø åπ â ÿ ËÕπ ÀâÀ ÿ π ÿ ˵âÕß æ Ë ß Èπ π Èπ ÀâÀ ÿπ ÿ ËÕπ ªìπ ...

Page 16: ...Õߪ Õ â π πµ Õß Õß ÿàπ ÁπÕ à ß J À àß à ø â µ ËÕߪ Õ πÕ SW5 G ËÕß â π πµ À H ËÕß â π πµ Õß SW5 1 ªî SW5 2 ªî SW5 3 ªî SW5 1 ªî SW5 2 ªî SW5 3 ªî SW5 K ËÕß â π πµ À L ËÕß â π πµ Õß SW5 1 ªî SW5 2 ªî SW5 3 ªî SW5 1 ªî SW5 2 ªî SW5 3 ªî µ Èß µ å DIP SW5 3 Õß Õ å ÿ ËÕߪ Õ π µ Èß µ å DIP SW5 3 Õß Õ å ÿ ËÕߪ Õ π ËÕµ Èß à ËÕß â π πµ Õß Àâµ Èß µ å DIP SW5 3 Õß Õ å ÿ ËÕߪ Õ π ª Ë ªî C D E F A B Fig 6 2 6 ß...

Page 17: ...240 V 5 â Õ å Ë à π º Õ à ßπâÕ 3 0 µà ßÀ π µà È Ëß ªìπ Õ å à âøî å NF À Õ Õ å π øøÑ Ë ß π NV 30 46 30 30 120 83 5 A B C F A H C D E G I I I H B B 1 B 1 B 1 B 1 B 1 B 2 B 2 B 2 B 2 B 2 Fig 6 5 A AB TB6 B Fig 6 4 J H Fig 6 6 6 3 Õπ 6 3 1 Õπ 1 ÈπµÕπ µ µ Èß 1 Õ µ Àπàß Ë µ µ Èß Õπ Fig 6 4 Áπ Õ åÕÿ À Ÿ µ µ Èß Èß Ë Õπ ËÕß π s À Èπ à πµàÕ ªπ È â µ à π Õß àÕß µ å ø 2 Èπ àÕ ø Õß ß π ß πÁÕµ À ÁÕ ªÑπ Õß A Ÿª ...

Page 18: ... s s s s sµàÕµ Àπàß Áπ ÿ ÿ Õß ÿ Õ π µÕ å ø MAC 397IF E â â π È A B A Áπµ Àπàß ç0é B Áπµ Àπàß ç1é C Áπµ Àπàß ç2é Fig 6 7 PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF A B D C G E F 4 1 2 1 3 4 1 2 6 4 µ Èß à øíß å π 6 4 1 µ Èßøíß å π Ë ËÕß Fig 6 7 ª Ë π à ß π øøÑ ë Õ à ª Ë π à ß π øøÑ µ ß π Õß øøÑ Ë â 1 ª Ë À µ Èß à øíß å π ªî Õπ ªÿÉ A B â ß âæ âÕ πÕ...

Page 19: ...N π π À 5 µ µ Õÿ À Ÿ ËÕß πÕ Õπ MA µ Ÿ Àâµ Èß à ªìπ OFF à Ëß À 6 ËÕß ÿàπ Mr Slim Õ Ÿà π ÿà À Õ à à ËÕß ÿàπ Mr Slim ËÕß ÿàπ Mr Slim µ Ÿ Àâµ Èß à ªìπ ON 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2 3 6 5 4 ON OFF 1 2...

Page 20: ... πÈ M àÕß Ÿ â N àÕߪ àÕ Õ ÕÕ O ª àÕ Àâ àÕß à ß æ ËÕÀ Ë ß Õ À ÿπ P µ ËÕß â π πÕ À Àµÿ ë àÕ π Õ à ßπâÕ 850 ë ËÕ µàÕµ ËÕßÀ Õß ËÕߪ Õ àÕ Àâ à π ë ß π µ π ß Ë Õß â ππÕ à 12 7 mmAq 124 Pa æ ÿàπ PEH ë µàÕ π àÕ Ÿ â E â È µàÕ π π Èπ ÀâµàÕ πÕ µ È µàÕ π â àÕߪ àÕ Õ ÕÕ F 1 1 1 2 2 2 2 3 3 3 4 4 4 6 1 2 3 5 A B C D 6 ß π π ø SW502 µ Èß à Õß ÿ Õ π µÕ å ø Àâµ ß À ß π Õß ËÕߪ Õ π ˵àÕ â â π Ÿ µ ß Ë 3 µ Õ À ß π Ÿà...

Page 21: ...âß π Õßµ ËÕߪ Õ π PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE C B A E D Fig 8 2 8 3 Àâ ËÕßµ Õ µ Õß Fig 8 2 1 ªî µ å 2 ªÿÉ CHECK Õß Èß 3 âªÿÉ TEMP µ Èß à ÁπÀ â ÿ 4 ªÿÉ ON OFF æ ËÕªî µ Õ µ Õß AªÿÉ CHECK B à Áπ CªÿÉ TEMP DIC ËÕߪ Õ π OC ËÕߪ Õ πÕ E À Á Fµ Àπàß ËÕß º ª µ ˵ æ Ë ËÕߪ Õ πÕ À µ Õ Õ À Àµÿ P1 àÕß Áπ Õ åº ª µ P2 P9 àÕ Áπ Õ åº ª µ...

Page 22: ...رارة درجة في خطأ مناظر ال E0 E3 السلكية بعد عن التحكم وحدة إشارات إرسال خطأ E4 E5 السلكية بعد عن التحكم وحدة إشارات إستقبال خطأ E1 E2 السلكية بعد عن التحكم وحدة لوحة خطأ السبب إلزالة التالي الجدول راجع أعاله الشتغيل اختبار تنفيذ بعد ً ممكنا الوحدة تشغيل يكن لم إذا األعراض األسباب السلكية بعد عن التحكم وحدة PLEASE WAIT التيار تشغيل بعد ً تقريبا دقيقتين لمدة صحيح التشغيل النظام تشغيل لبدء نتيجة وذلك...

Page 23: ...ام النظام مخطط مالحظات 1 MA بعد عن التحكم وحدة توصيل مباشرة الداخلية بالوحدة التحكم وحدة بين تختلف قد الشاش ت على تظهر التي المحتويات بعد عن التحكم ووحدة الداخلية بالوحدة الموصلة MA بعد ع ن الربط سطح بوحدة الموصلة MA أمثلة المروحة سرعة ح ّ المرش عالمة 2 السلكية بعد عن تحكم وحدة استعمال الداخلية الوحدة على الخارجي الوحدة الداخلية الوحدة MAC 397IF E الربط سطح PAR 21MAA MA بعد عن التحكم وحدة الالسلكي...

Page 24: ... ً دائما 12 6 الشكل 6 و 5 األرقام SW501 المفتاح إيقاف OFF على اضبط 5 رقم الغرفة حرارة درجة مستشعر MA بعد عن التحكم وحدة تشغيل ON الداخلية الوحدة إيقاف OFF ً موصال الربط سطح يكون عندما الحرارة درجات باستشعار MA بعد عن التحكم وحدة تقوم ال الموديل هذا في تشغيل ON على اضبط 6 رقم Mr Slim نظام وجود عدم أو وجود موجود Mr Slim نظام تشغيل ON موجود غير Mr Slim نظام إيقاف OFF SW500 المفتاح SW501 المفتاح 12 6 ...

Page 25: ...وظيفة إختيار الوظيفة بتهيئة القيام يمك ن ال 8 MAC 397IF E الربط سطح وحدة الى توصيله 9 6 الشكل وحدات عدة لتشغيل واحدة بعد عن تحكم وحدة استعمال يمكن باستعمال واحدة كمجموعة خارجية وحدة 16 أقصى حد وحدات عدة بتشغيل تسمح هذه الجماعي التحكم وظيفة واحدة بعد عن تحكم وحدة كل الداخلية التحكم بلوحة الخاصة CN105 CN92 بالموصيل MAC 397IF E الربط سطح بتوصيل قم 8 6 الشكل تبريد مادة عنوان MAC 397IF E 0 التبريد مادة...

Page 26: ...طوات بخصوص Sub الفرعي الداخلية B 1 B 2 5 6 الشكل 30 30 30 120 83 5 46 4 6 الشكل 6 6 الشكل الداخلية الوحدة موديل PE PEH الدفاية الداخلية للوحدة الكهربائي التيار إمداد أحادي N فولت 220 هرتز 60 فولت 240 220 هرتز 50 فولت 240 220 هرتز 50 أحادي N الدفاية الداخلية الوحدة دخل سعة الفيوز الرئيسي المفتاح أمبير 16 أمبير 16 أمبير 16 أمبير 16 أمبير 16 أمبير 16 األسالك عدد األسالك تمديدات 2 مم المقاس الدفاية ال...

Page 27: ...إمداد أنماط فقط التبريد لموديالت آني مزدوج نظام الحرارية المضخة لموديالت فقط التبريد لموديالت الخارجية للوحدة الكهربائي التيار إمداد Ⓐ أرضي تسرب قاطع Ⓑ عازل مفتاح أو أسالك دائرة قاطع Ⓒ الخارجية الوحدة Ⓓ الخارجية الوحدة الداخلية الوحدة توصيل أسالك Ⓔ السلكية بعد عن التحكم وحدة Ⓕ الحرارية المضخة لموديالت الداخلية الوحدة Ⓖ فقط التبريد لموديالت الداخلية الوحدة Ⓗ الداخلية للوحدة الكهربائي التيار إمداد Ⓙ...

Page 28: ... تأكد تثبيت طوق باستعمال األنبوب غطاء طرفي كال تثبيت من تأكد 2 وانزعه المتبقي الطوق ّ قص ⓡ الوصالت مواضع على فينيل شريط ق ِ ألص 3 بعد المصنع من الوحدة ش حن عند ً مغلقا الصمام يكون ً تماما مغلق الخارجية الوحدة على اإليقاف صمام أن من تحقق واألنابيب الداخلية الوحدة بين الغاز ب ّ تسر بفحص قم والخارجية الداخلية الوحدتين بين توصيالتاألنابيب جميع استكمال الخارجية الوحدة على اإليقاف صمام صيانة منفذ عبر ال...

Page 29: ... الداخلية دائرة توصيل عملية تكتمل بذلك بالكامل الخارجية الوحدة إيقاف صمامات افتح أعاله 2 و 1 الخطوتين استكمال بعد 3 الخارجية الوحدة على مبينة اإليقاف بصمامات الخاصة التعليمات والخارجية الداخلية الوحدتين بين التبريد مادة التوسيع صامولة شد قبل المشترك القاعدة وسطح االنبوب على بك الخاص التبريد زيت من رقيقة طبقة ضع األنابيب توصيالت شد إلحكام ربط مفتاحي استعمل المتضمنة للتعليمات ً تبعا ً جيدا اعزل الدا...

Page 30: ...جنب صفارة يطلق أن الساخن للهواء يمكن الحريق إنذار مستشعر نحو ً موجها الهواء نفث فيها يكون التي المواقع تجنب التدفئة تشغيل أثناء اإلنذار الحمضية المحاليل مناولة فيها تكثر التي األماكن تجنب غيره أو الكبريتي األساس ذات البخاخات استعمال فيها يكثر التي األماكن تجنب تحذير الوحدة وزن لتحمل كافية قوة ذو سقف على الداخلية الوحدة ثبت 2 2 الشكل الخدمة حيز 2 2 الموديالت A B PE H 2 5 3 650 690 PE H 4 920 960 PE...

Page 31: ...ة الوحدة من الماء قطرات تتساقط فقد ً ا مسدود التصريف أنبوب كان إذا أو 80 الغرفة رطوبة تجاوزت إذا ً ا أضرار تسبب أن المتساقطة الماء لقطرات يمكن حيث الداخلية الوحدة تركيب إلى تعمد ال للمحوالت يمكن اإلليكتروني والتداخل للضوضاء ً ا مس تعد كن اتصاالت مكتب أو مستش فى في الوحدة تركيب عند مكيف إصابة في تتسبب أن الالس لكية االتصاالت وأجهزة العالية الترددات ذات الطبية والمعدات المنزلية واألجهزة يتس بب وأن ا...

Page 32: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U935H02 Air Conditioners PEH 2 5 3 4 5 6EAK PEH 2 5 3 4 5EAKH PE 3 4 5 6EAK PE 3 4EAKT ...

Reviews: