background image

8

6.2. Remote controller (Fig. 6-2)
For wired remote controller

1) Installing procedures

(1) Select an installing position for the remote controller.
The temperature sensors are located on both remote controller and indoor unit.

s

Procure the following parts locally:

Two piece switch box
Thin copper conduit tube
Lock nuts and bushings

A

Remote controller profile

B

Required clearances surrounding the
remote controller

C

Installation pitch

30

46

30

30

120

83.5

A

B

C

(mm)

Fig. 6-2

(2) Seal the service entrance for the remote controller cord with putty to prevent pos-

sible invasion of dew drops, water, cockroaches or worms. (Fig.6-3)

A

For installation in the switch box:

B

For direct installation on the wall select one of the following:

• Prepare a hole through the wall to pass the remote controller cord (in order to run

the remote controller cord from the back), then seal the hole with putty.

• Run the remote controller cord through the cut-out upper case, then seal the cut-

out notch with putty similarly as above.

B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion:

F

A

H

C

D

E

G

I

I

I

H

B

(2)

(3)

B-1.

B-2.

Fig. 6-3

Fig. 6-4

C

Wall

D

Conduit

E

Lock nut

F

Bushing

G

Switch box

H

Remote controller cord

I

Seal with putty

J

Wood screw

J

H

(3) For direct installation on the wall (Fig.6-4)

6. Electrical work

*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. 120 m

For PUHZ-RP100/125/140 YHA application, use shield wires. The shield part must be grounded with the indoor unit OR the outdoor unit, NOT with both.

*3. The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4. The figures are NOT always against the ground.

Notes: 1. Wiring size must comply with the applicable local and national code.

2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer than other cables.

Indoor unit model
Indoor unit power supply
Indoor unit input capacity

*1

Main switch (Breaker)

Indoor unit power supply
Indoor unit power supply earth
Indoor unit-Outdoor unit

*2

Indoor unit-Outdoor unit earth
Remote controller-Indoor unit

*3

Indoor unit L-N

*4

Indoor unit-Outdoor unit S1-S2

*4

Indoor unit-Outdoor unit S2-S3

*4

Remote controller-Indoor unit

*4

PCA

~/N (single), 50 Hz, 230 V

16 A

×

 Min. 1.5

×

 Min. 1.5

×

 Min. 0.3

×

 0.3 (Non-polar)

AC 230 V

DC24 V
DC12 V

Circuit

rating

W

iring

W

ire No. 

×

 size

(mm

2

)

If the indoor and outdoor units have separate power supplies, refer to the table at the
below. If the optional wiring replacement kit is used, change the indoor unit electrical
box wiring refering to the figure in the right and the DIP switch settings of the outdoor
unit control board.

ON
OFF

1

2

(SW8)

3

Indoor power supply terminal kit (option)
Indoor unit electrical box connector con-
nection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)

Indoor unit specifications

Required

Required

Required

Electric heater
(For models with
heater)

Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit)

Indoor unit power supplied from outdoor unit
(when shipped from factory)

If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.

Connectors

Indoor unit

control board

Separate indoor unit/outdoor unit power
supplies

Electric heater
(For models with
heater)

S1

S2

S3

L

N

BLUE

BLUE

YELLOW

YELLOW

CND

CND

ORANGE

CND

ORANGE

S1

S2

S3

L

N

YELLOW

BLUE

BLUE

YELLOW

CND

Indoor unit

control board

* There are three types of labels (labels A, B, and C). Affix the appropriate labels to

the units according to the wiring method.

Summary of Contents for Mr. Slim PCA-RP-HAQ

Page 1: ...are il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ ÚÈ...

Page 2: ...ons office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communications equip ment harming the screen display quality Thermal insulation of the refrigerant pipe ...

Page 3: ...sion bolts or use angle stock braces or square timbers for bolt installation Fig 3 4 3 Selection of suspension bolts and tubing positions Fig 3 3 Using the pattern paper provided for installation select proper positions for suspen sion bolts and tubing and prepare relative holes 3 2 Preparation for installation Fig 3 2 1 Suspension bolt installing spacing mm Models A B RP71 1180 1136 RP125 1564 15...

Page 4: ...he below Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric com pounds oxidants debris or dust Warning When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refriger ant and do not allow air to remain in the lines Air enclosed in the lines can cause ...

Page 5: ...copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare n...

Page 6: ...upplied with the unit to the drain hose 5 3 Connect the drain hose 5 to the drain hole of the unit 4 Connect the field drain tubing VP 25 O D ø32 PVC TUBE to the drain hose 5 5 Tighten the band 6 in 2 places 6 Wrap the drain tubing cover 7 supplied with the unit 7 Install the independent piece 8 Check for correct drainage Fill the drain pan with water of about 1 L from the tubing sensor access por...

Page 7: ...prene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Heater Indoor unit input capacity Heater 1 Main switch Breaker Indoor unit power supply Heater Indoor unit power supply Heater earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit earth 2 Remote controller Indoor unit 3 Indoor unit Heater L N 4 Indoor unit Outd...

Page 8: ...code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Indoor unit input capacity 1 Main switch Breaker Indoor unit power supply Indoor unit power supply earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit e...

Page 9: ...ts of the setting can be confirmed 9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear A To TB5 on the indoor unit B TB6 No polarity 2 Connecting procedures Fig 6 5 Connect the remote controller cord to the terminal block 3 Two remote controller setting If two re...

Page 10: ...em control is used 4 Press the ON OFF button to stop the self check C C SIMPLE PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF TEST RUN COOL HEAT A F C E D B M I H G A ON OFF button B Test run display C Indoor temperature liquid line tem perature display D ON OFF lamp E Power display F Error code display Test run remaining time display G Set temperatu...

Page 11: ...ates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units Indicates state of communication between the indoor and outdoo...

Page 12: ... press the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Di...

Page 13: ...C This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K Printed in Japan RG79D721H01 The product at hand is based on the following EU regulations ...

Reviews: