7
TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the
table below. Check the contents below before investigating details.
7-1. TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (7-3).
Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
The trouble is not reoccurring.
Logged
Not logged
1
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, and wiring related.
2
Reset error code logs and restart the unit after finishing
service.
3
There is no abnormality in electrical components,
controller boards, and remote controller.
1
Recheck the abnormal symptom.
2
Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
3
Continue to operate unit for the time being if the cause
is not ascertained.
4
There is no abnormality in electrical components,
controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1
Turn on the power.
2
Press the [CHECK] button twice.
3
Set address with [TEMP] button if system control is used.
4
Press the [ON/OFF] button to stop the self-check.
A
CHECK button
B
Address
C
TEMP. button
D
IC : Indoor unit
OC: Outdoor unit
E
Check code
F
Unit No.
G
Timer ON/OFF button
A
F
C
B
B
E
E
D
G
<To cancel check code>
1
Display the error code at the self-check result display screen.
2
The address for self-check will blink when the
G
ON/OFF
button is pressed twice within 3 seconds.
– – – – : No trouble generated in the past
F F F F : No corresponding unit
7-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
■
Wired remote controller
OC382B--1.qxp 08.2.19 8:29 AM Page 27