3-3 . OUTLET AIR SPEED AND COVERAGE RANGE
Airflow
Air speed
Coverage range
Airflow
Air speed
Coverage range
m
3
/min
m/sec.
m
ft
m
3
/min
m/sec.
m
ft
Configuration
50Hz
Frequency
60Hz
Model
PC-4GAKD
25
4.1
12.6
41.6
25
4.1
12.6
41.6
PC-5GAKD
34
4.38
15.2
50.0
34
4.38
15.2
50.0
PC-6GAKD
34
4.38
15.2
50.0
34
4.38
15.2
50.0
PC-3GAKD
18
3.8
10.4
34.5
18
3.8
10.4
34.5
PC-2.5GAKD
18
3.8
10.4
34.5
18
3.8
10.4
34.5
Ceiling suspended
PC-2GAKD
13
3.7
8.8
29
13
3.7
8.8
29
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International
Organization for Standardization).
The conversion factor is : 1(MPa)=10.2(kgf /
F
F
)
Capacity
Input
Indoor unit Model
Phase, Hz
Voltage
Current
Outdoor unit Model
Phase, Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V
A
V
A
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
D.B.
W.B.
D.B.
D.B.
W.B.
Model
Electrical circuit
T
otal
Refrigerant circuit
Indoor side
Outdoor
side
MODE
MPa
(kgf/
F
)
MPa
(kgf/
F
)
PC-2GAKD PC-2.5GAKD
PC-3GAKD
PC-4GAKD
PC-5GAKD PC-6GAKD
Cooing
5500
6500
7600
10300
13200
15200
1.91
2.33
3.31
3.61 / 3.54
4.27
5.26
PC-2GAKD PC-2.5GAKD PC-3GAKD
PC-4GAKD
PC-5GAKD PC-6GAKD
1, 50
1, 50
1, 50
1, 50
1, 50
1, 50
220
220
220
220
220
220
0.38
0.51
0.51
0.68
0.96
0.96
PU-2VAKD PU-2.5VAKD PU-3VAKD
PU-4VAKD/
PU-4YAKD
PU-5YAKD
PU-6YAKD
1, 50
1, 50
1, 50
1 / 3 , 50
3, 50
3, 50
220
220
220
220 / 380
380
380
8.4
10.3
15.1
17.5 / 5.9
7.2
9.0
1.90
(19.4)
2.07
(21.1)
2.13
(21.8)
1.96
(20.0)
1.90
(19.4)
2.06
(21.0)
0.49
(5.0)
0.53
(5.4)
0.47
(4.8)
0.51
(5.2)
0.44
(4.5)
0.41
(4.2)
78.5
80
83.7
77.1
76
81.6
47.7
54.4
55.5
51.2
47.5
52.8
3.7
6.9
3.2
6.9
3.5
2
5
5
5
5
5
5
27
27
27
27
27
27
19
19
19
19
19
19
12.4
13.5
12.4
12.5
13.0
11.6
35
35
35
35
35
35
24
24
24
7700
3.05
PC-3GAKD
1, 50
230
0.53
PU-3VAKR
1, 50
230
12.6
1.64
(16.7)
0.43
(4.4)
79.8
44.7
1.8
7.5
27
19
12.1
35
24
24
9550
3.82
PC-4GAKD
1, 50
230
0.69
PU-4VAKR
1, 50
230
16.6
1.92
(19.6)
0.51
(5.2)
75.8
48.2
6.4
7.5
27
19
13.1
35
24
24
24
w
The air coverage range is the distance to which the 0.25 m/sec. air can reach when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the fur-
niture inside the room.
OC382B--1.qxp 08.2.19 8:28 AM Page 15