13
Cooling Capacity Correction Factors
(Outdoor unit:PU-J type)
50Hz
Model
Refrigerant piping length (one way)
5m(16ft)
10m(33ft)
15m(49ft)
20m(66ft)
25m(82ft)
30m(98ft) 35m(115ft) 40m(131ft) 45m(148ft) 50m(164ft)
Cooling Capacity Correction Factors
60Hz
Model
Refrigerant piping length (one way)
5m(16ft)
10m(33ft)
15m(49ft)
20m(66ft)
25m(82ft)
30m(98ft) 35m(115ft) 40m(131ft)
PC-2GAKD
1.0
0.985
0.975
0.964
0.954
0.944
—
—
PC-2.5GAKD
1.0
0.978
0.963
0.948
0.934
0.921
—
—
PC-3GAKD
1.0
0.971
0.950
0.931
0.913
0.896
—
—
PC-4GAKD
1.0
0.980
0.966
0.952
0.939
0.826
0.914
0.902
45m(148ft) 50m(164ft)
—
—
—
—
—
—
—
—
PC-5GAKD
1.0
1.0
0.971
0.960
0.950
0.933
0.931
0.908
0.913
0.885
0.896
0.864
0.880
0.845
0.864
0.828
0.850
0.840
0.812
0.800
PC-6GAKD
PC-2GAKD
PC-2.5GAKD
PC-3GAKD
PC-4GAKD
PC-5GAKD
PC-6GAKD
1.0
1.0
1.0
1.0
1.0
1.0
0.985
0.983
0.978
0.978
0.978
0.970
0.975
0.972
0.962
0.974
0.962
0.950
0.964
0.961
0.948
0.964
0.948
0.931
0.954
0.951
0.934
0.954
0.934
0.912
0.944
0.940
0.921
0.944
0.921
0.896
—
—
—
0.935
0.908
0.880
—
—
—
0.926
0.896
0.864
—
—
—
—
0.884
0.850
—
—
—
—
0.875
0.840
Cooling Capacity Correction Factors
(Outdoor unit:PU-AKD type)
50Hz
Model
Refrigerant piping length (one way)
5m(16ft)
10m(33ft)
15m(49ft)
20m(66ft)
25m(82ft)
30m(98ft) 35m(115ft) 40m(131ft) 45m(148ft) 50m(164ft)
PC-2GAKD
PC-2.5GAKD
PC-3GAKD
PC-4GAKD
PC-5GAKD
PC-6GAKD
1.0
1.0
1.0
1.0
1.0
1.0
0.985
0.983
0.978
0.984
0.978
0.970
0.975
0.972
0.962
0.974
0.962
0.950
0.964
0.961
0.948
0.964
0.948
0.931
0.954
0.951
0.934
0.954
0.934
0.912
0.944
0.940
0.921
0.944
0.921
0.896
—
—
—
0.935
0.908
0.880
—
—
—
0.926
0.896
0.864
—
—
—
—
0.884
0.850
—
—
—
—
0.875
0.840
Cooling Capacity Correction Factors
(Outdoor unit:PU-AKR type)
50Hz
Model
Refrigerant piping length (one way)
5m(16ft)
10m(33ft)
15m(49ft)
20m(66ft)
25m(82ft)
30m(98ft) 35m(115ft) 40m(131ft) 45m(148ft) 50m(164ft)
PC-3GAKD
PC-4GAKD
1.0
1.0
0.978
0.984
0.962
0.974
0.948
0.964
0.934
0.954
0.921
0.944
—
0.935
—
0.926
—
—
—
—
OC382B--1.qxp 08.2.19 8:28 AM Page 13