background image

6

Copper
pipe

Good

No good

Tilted Uneven Burred

Burr

Copper pipe

Spare
reamer

Pipe cutter

Flare nut

Copper pipe

5-3

FLARING WORK

• Main cause of gas leakage is defect in flaring work.

Perform flaring work correctly in the following procedure.

1. Pipe cutting

• Cut the copper pipe correctly with pipe cutter.

2. Burrs removal

• Completely remove all burrs from the cut cross

section of the pipe.

• Put the end of the copper pipe downward to pre-

vent burrs from dropping in the pipe.

3. Putting nut on

• Remove flare nuts attached to indoor and outdoor

units, then put them on pipe having completed
burr removal.
(not possible to put them on after flaring work)

• Flare nut for R410A pipe may differ from R22 pipe

depending on the diameter of pipe.

Smooth all around

Even length
all around

Inside is shining without any scratches

4. Flaring work

• Carry out flaring work using flaring tool as shown below.

Outside diameter

A

mm

inch

Flare tool for R410A

ø6.35

1/4

0.06 to 0.08

ø9.52

3/8

0.06 to 0.08

ø12.7

1/2

0.08 to 0.10

Firmly hold copper pipe in a die in the dimension shown in the
table above.

5. Check

• Compare the flared work with the figure below.
• If flare is noted to be defective, cut off the flared section

and perform flaring work again.

5-4

PIPE CONNECTION

Note:
Fasten a flare nut with a torque wrench as specified in the table below.
When fastened too tight, a flare nut may be broken after a long period and cause a leakage of refriger-
ant.

1. Indoor unit connection

• Connect both liquid pipe and gas pipe to indoor unit.

- Apply a thin coat of refrigeration oil to the seat surface of pipe.
- For connection, align the center of both pipe and union, then tighten the first 3 to 4 turns in flare nut by

hand.

- For tightening the union part of the indoor unit side, use the table below as a standard and tighten

the flare nut with two wrenches. Excessive tightening damages the flared section.

Pipe diameter

Tightening torque

mm

inch

ft. · Ib

ø6.35

1/4

10 to 13

ø9.52

3/8

25 to 30

ø12.7

1/2

36 to 42

2. Outdoor unit connection

• Connect pipes to the pipe joint part of the stop valve in the same method as the indoor unit.

- For tightening, use the same tightening torque applied for indoor unit and tighten the flare nut with

torque wrench or spanner.

INSULATION AND TAPING

1

Cover piping joints with pipe cover.

2

For outdoor unit side, surely insulate every piping including valves.

3

Using piping tape 

E

, apply taping starting from the entry of outdoor unit.

• Fix the end of piping tape 

E

 with adhesive tape.

• When piping has to be arranged through above ceiling, closet or area where the temperature and humidity

are high, wind additional commercially sold insulation for prevention of condensation.

*

Connections at outdoor unit are described as unit A and B below corresponding to the indication on
each valve.

• If the diameter of connection pipes does not match the diameter of pipe end connections, use optional

different-diameter joints.

• When connecting the model 15, use optional different-diameter joints MAC-A454JP because the valve size

of gas pipes for the outdoor unit is ø9.52 mm (3/8 in.).

PIPING PREPARATION

1

If you use commercially available copper pipes, use the following table for pipe specifications.

Outside diameter

Minimum Wall thickness

Insulation thickness

Insulation material

mm (in.)

mm (in.)

mm (in.)

Liquid pipe

ø6.35 (1/4)

0.80 (0.0315)

8 (5/16)

Gas pipe

ø9.52 (3/8)

0.80 (0.0315)

8 (5/16)

Gas pipe

ø12.7 (1/2)

0.80 (0.0315)

8 (5/16)

2

Ensure that the 2 refrigerant pipes are insulated to prevent condensation.

3

Refrigerant pipe bending radius must be 4 in. or more.

 CAUTION:

Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installa-
tion of the indoor unit and lack of thickness may cause dew drippage.

90

°

Heat resisting from
plastic 0.045 Specific
gravity

Model

Pipe size for indoor unit

Allowable

name

[mm (in.)]

connection pipe size

09

Liquid pipe

ø6.35 (1/4)

ø6.35 (1/4)

12

Gas pipe

ø9.52 (3/8)

ø9.52 (3/8)

15

Liquid pipe

ø6.35 (1/4)

ø6.35 (1/4)

Gas pipe

ø12.7 (1/2)

ø12.7 (1/2)

SELECTING PIPE SIZE

The diameter of connection pipes differs according to the type and capacity of indoor units. Match the diameters
of connection pipes for indoor and outdoor units according to the following table.

A

Die

Copper pipe

Flare nut

Die

Copper pipe

York

Flaring tool

Clutch type

Valve size for outdoor unit

mm (in.)

Å

 UNIT

Liquid pipe

ø6.35 (1/4)

Gas pipe

ø9.52 (3/8)

ı

 UNIT

Liquid pipe

ø6.35 (1/4)

Gas pipe

ø9.52 (3/8)

Summary of Contents for Mr.Slim MXZ-2A20NA

Page 1: ...TIONERS Model INSTALLATION MANUAL MXZ 2A20NA FLARE CONNECTION TYPE ATTENTION This manual mentions how to install only the outdoor unit MXZ 2A20NA As for the way of installation for indoor unit MSZ A09NA MSZ A12NA and MSZ A15NA please refer to the installation manual being attached each indoor unit The installation manual details the suggested installation method Any structural alterations necessar...

Page 2: ...mplete connecting and fixing could cause fire Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet It could cause a fire or an electric shock due to de fective contact defective insulation exceeding the permissible current etc Check that the refrigerant gas due not leak after installation has completed If refrigerant gas leaks ...

Page 3: ...required for the affected device Install the unit horizontally Please install it in an area not affected by snowfall or blowing snow In areas with heavy snow please install a canopy a pedestal and or some baffle boards Note It is advisable to make a piping loop near outdoor unit so as to reduce vibration transmitted from there WARNING Be sure to install the unit in a place that well sustains its w...

Page 4: ... supply circuit between indoor and outdoor unit depending on local code FREE SPACE REQUIRED AROUND OUTDOOR UNIT Unit mm inch 350 13 78 or more 100 3 94 or more 1 Top side obstacles When there is an obstacle behind the rear side only it does not matter if there is an obstacle over the top side as shown in the figure below 2 Front blowing side open As long as space like the one shown in the figure c...

Page 5: ...2 tools be used Description Gauge manifold No R410A has high pressures beyond the measurement range of existing gauges Charge hose No Hose material and cap size have been changed to improve the pressure resist ance Gas leak detector No Dedicated for HFC refrigerant Torque wrench Yes 1 4 and 3 8 No 1 2 Flare tool Yes Clamp bar hole has been enlarged to reinforce the spring strength in the tool Flar...

Page 6: ...it For tightening use the same tightening torque applied for indoor unit and tighten the flare nut with torque wrench or spanner INSULATION AND TAPING 1Cover piping joints with pipe cover 2For outdoor unit side surely insulate every piping including valves 3Using piping tape E apply taping starting from the entry of outdoor unit Fix the end of piping tape E with adhesive tape When piping has to be...

Page 7: ...ated fully open all stop valves on both sides of gas pipe and liquid pipe Operating without fully opening lowers the performance and this causes trouble Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test or the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R410A 0 ...

Page 8: ... in the system and affect normal operation of the air conditioner Also charge the system slowly otherwise the compressor will be locked Indoor unit Union Stop valve Outdoor unit Union Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder operating valve for R410A Refrigerant gas cylinder for R410A with siphon Refrigerant liquid Electronic scale for refrigerant charging Liqu...

Page 9: ...S DE AIRE DE TIPO DIVIDIDO Modelo MANUAL DE INSTALACIÓN MXZ 2A20NA TIPO DE CONEXIÓN ABOCARDADA ATENCIÓN Este manual corresponde únicamente a la instalación de la uni dad exterior MXZ 2A20NA Para la instalación de las unidades interiores MSZ A09NA MSZ A12NA y MSZ A15NA consulte el manual de instalación que se incluye en cada unidad interior El manual de instalación detalla el método de instalación ...

Page 10: ...sas podrían provocar un in cendio No emplee conexiones intermedias del cable de alimen tación ni tampoco un cable alargador evite también co nectar demasiados aparatos a una sola toma de CA Esto podría provocar un incendio o una descarga eléctrica a causa de un contacto o un aislamiento defectuoso un exce so de corriente etc Una vez acabada la instalación compruebe que no haya una fuga de gas refr...

Page 11: ...or sea baja observe las instruc ciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entrada salida de aire quede expuesto directamente al viento Para evitar la exposición al viento instale la unidad exterior con el lado de entrada de aire hacia la pared Para evitar la exposición al viento se recomienda instalar una placa deflectora en el lado de salida de aire de...

Page 12: ...de alimentación entre las unidades interior y exterior depen diendo de la normativa local ESPACIO LIBRE NECESARIO ALREDEDOR DE LA UNIDAD EXTERIOR unidad mm pulg 350 13 78 o más 100 3 94 o más 1 Obstáculos en la parte superior Cuando hay un obstáculo en la parte trasera no importa si hay algún obstáculo por encima de la unidad tal y como se muestra en la siguiente ilus tración 2 Parte delantera ven...

Page 13: ...IA DE ALTURA Límites 2A20NA Longitud de tubería por unidad interior 25 m 82 pies máx Longitud total de tubería por multisistema 50 m 164 pies máx Diferencia de altura 10 m 33 pies máx N º encorvaduras por unidad interior 25 máx N º total encorvaduras por multisistema 50 máx Ajuste de refrigerante Si la longitud de la tubería es superior a 40 m 131 pies será necesario emplear más refrigerante R410A...

Page 14: ...rior Para el apriete utilice el mismo par aplicado en la unidad interior y apriete la tuerca abocardada con una llave dinamométrica o una llave de tuercas AISLAMIENTO TÉRMICO Y FORRADO CON CINTA 1Cubra las uniones de tuberías con cubiertas de tubería 2En el lado de la unidad exterior aísle bien cada una de las tuberías y válvulas 3Aplique cinta de tuberías E a partir de la entrada de la unidad ext...

Page 15: ...a por completo todas las válvulas de retención de ambos lados del tubo de gas y del tubo de líquido Si no se lleva a cabo esta operación abriendo dichas válvulas por completo el rendi miento disminuirá y se producirán problemas Apriete la tapa del puerto de servicio para volver al estado inicial Vuelva a apretar la tapa Prueba de fugas o la bomba de vacío con la función de evitar el reflujo Válvul...

Page 16: ...de alterarse en el siste ma y afectar al funcionamiento normal del aparato de aire acondicionado Recuerde también cargar el sistema poco a poco ya que de lo contrario puede bloquear el compresor Unidad interior Unión Válvula de retención Unidad exterior Unión Válvula colectora de manómetro para R410A Manguera de carga para R410A Válvula de accionamiento del cilindro de gas refrigerante para R410A ...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SG79Y666H01 ...

Reviews: