24
3) HEATING CAPACITY
Model
Indoor air
Outdoor intake air WB temperature (
˚
F)
IDB
5
15
25
35
43
45
55
(
˚
F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
MUZ-A09NA
MUZ-A09NA -
U1
75
—
—
6.3 0.64 7.9 0.75 9.4 0.84 10.6 0.88 11.0 0.89 12.4 0.93
70
6.7 0.62 8.2 0.74 9.6 0.82 10.9 0.86 11.2 0.88 12.7 0.91
65
6.9 0.59 8.6 0.71 10.0 0.80 11.2 0.84 11.6 0.85 13.0 0.89
MUZ-A09NA -
1
MUZ-A09NA -
U2
75
—
—
6.3 0.64 7.9 0.75 9.4 0.84 10.6 0.88 11.0 0.89 12.4 0.93
70
6.7 0.62 8.2 0.74 9.6 0.82 10.9 0.86 11.2 0.88 12.7 0.91
65
6.9 0.59 8.6 0.71 10.0 0.80 11.2 0.84 11.6 0.85 13.0 0.89
MUZ-A12NA
75
—
—
7.9 0.86 9.9 1.02 11.8 1.13 13.3 1.19 13.7 1.21 15.5 1.25
70
8.4 0.84 10.2 0.99 12.0 1.10 13.6 1.16 14.0 1.18 15.8 1.23
65
8.6 0.80 10.7 0.96 12.4 1.07 14.0 1.13 14.4 1.15 16.2 1.21
MUZ-A15NA
75
—
—
10.4 1.33 13.1 1.57 15.6 1.75 17.6 1.83 18.1 1.86 20.5 1.93
70
11.1 1.29 13.5 1.53 15.9 1.70 18.0 1.79 18.5 1.83 21.0 1.90
65
11.3 1.24 14.1 1.48 16.5 1.66 18.5 1.75 19.1 1.77 21.4 1.86
MUZ-A17NA
75
—
—
11.7 1.60 14.6 1.88 17.4 2.10 19.6 2.20 20.2 2.24 22.9 2.32
70
12.4 1.55 15.1 1.84 17.8 2.04 20.1 2.15 20.7 2.19 23.4 2.28
65
12.7 1.48 15.8 1.77 18.4 1.99 20.7 2.10 21.3 2.13 23.9 2.24
MUZ-A24NA
75
—
—
13.5 1.75 16.8 2.06 20.1 2.29 22.6 2.41 23.3 2.44 26.4 2.54
70
14.3 1.69 17.4 2.01 20.5 2.23 23.2 2.35 23.9 2.40 27.0 2.49
65
14.6 1.62 18.2 1.94 21.2 2.17 23.9 2.29 24.6 2.33 27.6 2.44
MUZ-GA24NA
75
10.2
1.26
13.5
1.59
16.8
1.87
20.1
2.09
22.6
2.19
23.3
2.23
26.4
2.31
70
11.0
1.21
14.3
1.54
17.4
1.83
20.5
2.03
23.2
2.14
23.9
2.18
27.0
2.27
65
11.6
1.16
14.6
1.48
18.2
1.77
21.2
1.98
23.9
2.09
24.6
2.12
27.6
2.23
NOTE
: 1. IDB: Intake air dry-bulb temperature
TC: Total Capacity (×10
3
Btu/h)
TPC: Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on
the remote controller.
Summary of Contents for Mr.Slim MUZ-A17NA
Page 12: ...12 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA 5 WIRING DIAGRAM ...
Page 13: ...13 MUY A15NA MUY A17NA ...
Page 14: ...14 MUZ A24NA MUZ A24NA U1 ...
Page 15: ...15 MUZ A24NA 1 MUZ A24NA U2 ...
Page 16: ...16 MUY A24NA ...
Page 17: ...17 MUY A24NA 1 ...
Page 18: ...18 MUZ GA24NA ...
Page 19: ...19 MUY GA24NA ...