11
ACH50-50 plates
Mode
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Total
Capacity
W
12,000
14,000
12,500
16,000
Input
kW
5.10
3.37
5.38
4.10
Electrical
circuit
Outdoor unit
PUHZ-RP125VHA2#2/
PUHZ-RP125YHA2#2
PUHZ-RP140VHA2#2/
PUHZ-RP140YHA2#2
Phase, Hz
1 / 3, 50
1 / 3, 50
Voltage
V
230 / 400
230 / 400
Current
A
22.4 / 7.6
15.0 / 5.2
23.6 / 8.1
18.2 / 6.2
Refrigerant circuit
Discharge pressure
MPa
2.8
2.1
2.8
2.2
Suction pressure
MPa
0.7
0.7
0.7
0.7
Discharge temperature
:
80
69
81
67
Condensing temperature
:
46
36
46
36
Suction temperature
:
3
4
3
1
Evaporating temperature
:
5
-1
5
-1
Evaporator inlet temperature
:
6
—
6
—
Evaporator outlet temperature
:
5
—
5
—
Condenser inlet temperature
:
—
63
—
61
Condenser outlet temperature
:
—
35
—
34
Water
conditions
Flow volume
L/min
34.4
40.1
35.8
45.9
Outlet water temperature
:
7
35
7
35
Outdoor
conditions
Intake air temperature
D.B.
:
35
7
35
7
W.B.
:
24
6
24
6
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/