10
(2) PUHZ-RP • VHA3/YHA3(2)
ACH50-30 plates
ACH50-50 plates
Mode
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Total
Capacity
W
6,000
7,000
6,600
8,000
9,100
11,200
Input
kW
2.31
1.63
2.59
1.90
3.31
2.66
Electrical circuit
Outdoor unit
PUHZ-RP60VHA3#1
PUHZ-RP71VHA3#1
PUHZ-RP100VHA3#1/
PUHZ-RP100YHA3#1
Phase, Hz
1, 50
1, 50
1/3, 50
Voltage
V
230
230
230 / 400
Current
A
10.3
7.2
11.4
8.4
14.5 / 5.1
11.8 / 4.1
Refrigerant circuit
Discharge pressure
MPa
2.7
2.1
2.7
2.2
2.6
2.1
Suction pressure
MPa
0.8
0.7
0.8
0.7
0.8
0.7
Discharge temperature
:
70
65
70
66
74
65
Condensing temperature
:
45
36
45
36
44
36
Suction temperature
:
4
5
4
2
6
5
Evaporating temperature
:
5
1
5
1
5
1
Evaporator inlet temperature
:
6
—
6
—
5
—
Evaporator outlet temperature
:
5
—
5
—
5
—
Condenser inlet temperature
:
—
56
—
57
—
58
Condenser outlet temperature
:
—
34
—
33
—
35
Water
conditions
Flow volume
L/min
17.2
20.1
18.9
22.9
26.1
32.1
Outlet water temperature
:
7
35
7
35
7
35
Outdoor
conditions
Intake air temperature
D.B.
:
35
7
35
7
35
7
W.B.
:
24
6
24
6
24
6
The unit of pressure has been changed to MPa based on international SI system.