4. PARAMETERS
4 - 6
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
PN32
*IPOA2
Operation
specification
IP address 2
Set the 2nd octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN31] to [Pr. PN34] are all set to "0", the function is disabled.
When the function is enabled, the servo amplifier allows the following data 1) to be
imported only if the IP address of the client (external device) matches with the
operation specification IP address. If they are mismatched, the data is discarded.
1) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
0
PN33
*IPOA3
Operation
specification
IP address 3
Set the 3rd octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN31] to [Pr. PN34] are all set to "0", the function is disabled.
When the function is enabled, the servo amplifier allows the following data 1) to be
imported only if the IP address of the client (external device) matches with the
operation specification IP address. If they are mismatched, the data is discarded.
1) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
0
PN34
*IPOA4
Operation
specification
IP address 4
Set the 4th octet of the IP address of the network device allowed to be connected in
decimal.
When [Pr. PN31] to [Pr. PN34] are all set to "0", the function is disabled.
When the function is enabled, the servo amplifier allows the following data 1) to be
imported only if the IP address of the client (external device) matches with the
operation specification IP address. If they are mismatched, the data is discarded.
1) Modbus/TCP function code 10h
Monitoring, parameter setting, and test operation can be executed via Ethernet when
the IP addresses of a personal computer (MR Configurator2) and GOT are within the
range of the operation specification IP address. When out of the range,
communication to the servo amplifier cannot be established.
Setting range: 0 to 255
0
PN35
*IPOR3
Operation
specification
IP address 3
range
specification
Set a value for the 3rd octet range of the IP address of the network device allowed to
be connected.
The range for the IP address of the network device allowed to be connected is
between [Pr. PN33] and [Pr. PN35]. Set a value in decimal.
Setting "256" will disable the function.
Setting range: 0 to 256
256
PN36
*IPOA4
Operation
specification
IP address 4
range
specification
Set a value for the 4th octet range of the IP address of the network device allowed to
be connected.
The range for the IP address of the network device allowed to be connected is
between [Pr. PN34] and [Pr. PN36]. Set a value in decimal.
Setting "256" will disable the function.
Setting range: 0 to 256
256